'Operation' task card
Person Machine Interface (PMI)
13
259 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
13.1.3 Country settings
Country-specific settings are defined in the 'Country settings' element.
13.1.4 Master clock
The 'Global system time' element shows which
'Station' is the master clock.
When the first 'Station' is created, Cerberus-Engineering-Tool assigns this element
to the first 'Station' (address 1) automatically. The
assignment to the 'Station'
may therefore be deleted or need to be changed. If this is the case, then the
assignment must be created again.
Figure 85: Assign master clock
To assign the master clock, proceed as follows:
1. Select the 'Operation' task card.
2. Open 'Global system configuration' in the tree view.
3. Highlight 'Global system time'.
4. In the menu bar, click on 'Assign'.
a
The 'New effect dialog' window opens.
a
At the right in the window, the 'Hardware tree' is displayed.
5. Select the relevant 'Station' and click on 'Assign'.
a
'Global system time' is assigned to the 'Station'.
13.2 Person Machine Interface (PMI)
The 'PMI' element contains the configurable elements of the Person Machine
Interface:
●
Basic settings
●
'LEDs'
●
'Standard keys'
●
'Favorite keys'
● ↑
Visibility
You will find information on these elements in the following chapters.