'Control' task card
Damper control group
12
240 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
12.6.6 EDE export
●
Contains the BACnet parameters for the damper controls
●
Can be used for the configuration of Desigo PX controllers
●
Software required: XSLT processor for converting the SiB-X export on the
basis of an XSLT style sheet
– Example: Command Line Transformation Utility (msxsl.exe)
●
Provided by FS720: XSLT style sheet
Generating an EDE export
w
You have an XSLT processor or equivalent software with this functionality, e.g.,
msxsl.exe.
w
You have created and configured the damper controls. Link [
1. Perform the SiB-X export for the site in Cerberus-Engineering-Tool. Link [
2. In Cerberus-Engineering-Tool, select 'Help' menu > 'View additional
documents' > 'EDE_export'.
– The XSLT style sheet can be found inside the 'EDE_export' directory in
XSL format.
3. Use the SiB-X export as an input document and the XSL file as a style sheet
for generating the EDE export in your XSLT processor.
The EDE export only contains the BACnet parameters for the damper controls. It
does not contain BACnet parameters for any other site elements.
12.6.7 Configuring LEDs for damper control
The state of the fire and/or smoke dampers can be displayed on an LED indicator
FTO200x.
Example: State of a fire damper displayed by means of two LEDs on LED indicator
FTO2008
●
LED 1 lights up green: Damper open
●
LED 1 lights up red: Damper closed
●
LED 1 and 2 off: Damper moving, i.e., is in the process of closing or opening
●
LED 1 off, LED 2 lights up yellow:
– Timeout occurred while opening or closing the damper
– Damper is unexpectedly open or unexpectedly closed
– Fault
Configuring an LED indicator
1. Select the 'Hardware' task card and create an LED indicator FTO2008 for the
relevant station.
2. Go to the 'Overview' tab and set the address of the LED indicator to a value of
between 20 and 35 in accordance with the DIP switch setting on the LED
indicator.
3. Select the 'Operation' task card and create the 'LED ind./mimic 48 LEDs'
element for the relevant station.
4. Assign the 'LED ind./mimic 48 LEDs' element to the LEDs of the FTO2008 in
the hardware tree.