9 Technical data
Supply
Operating voltage
DC 24 V
Standby power consumption
95 mA @24 V
Built-in power consumption, supply via
MoNetBus or AUX power
Max. 380 mA @ 24 V
Power consumption via PoE
Max. 185 mA @ 24 V
Ethernet interfaces
Sockets
4x RJ45, 10/100 Mbit/s
Length of line
●
P4, P5 'Local', limited to same
housing but must be min. 2 m
●
P2, P3 'Field', limited to same room
but must be min. 2 m, max. 6 m
Connectors
External supply input
4-pin plug-in terminal
Fault terminal
4-pin plug-in terminal
●
Fault output 'F1', 'F2'
Dry contact relay (common)
Switching current max. 1 A, resistive
Switching voltage max. DC 30 V
MoNetBus
22-pin flat-cable connector
External Ethernet connections 'P2', 'P3'
●
Additional voltage surge protection
●
Increased EMC protection
●
Ground fault supervision
Circuits
●
All connections are power limited
●
All connections – except local and
MoNet connections – are supervised
Module connections
(optional)
Ethernet module (electric) VN2001
RJ45 connection (TP), cable length max.
330 ft/100 m
Ethernet module (MM) VN2002
LC connector, multi-mode fiber optic
●
Fiber length 62.5/125°µm:
13123 ft/4 km with an 11 dB loss
1
●
Fiber length 50/125°µm: 6561 ft/2 km
with a 7.5 dB loss
1
Ethernet module (SM) VN2003
LC connector, single-mode fiber optic:
●
Fiber length 9/125°µm:
131233 ft/40 km with a 29 dB loss
1
Mechanical data
Dimensions (W x H x D), with cover,
without optional modules
165 x 121 x 43 mm
Weight
560 g/1.2 lbs
Ambient conditions
For indoor use in dry rooms only
Operating temperature
120+/-3°F to 32+/-3°F
Rel. humidity during operation
93+/-2% at a temperature of 90+/-3°F
Protection category
IP30
1
The length is a guide value dependent upon the loss of the cable used, the loss of the
connector types used, and the transmission losses that are present. The
corresponding values must be taken from the respective data sheets.
Technical data
9
A6V10407862_e_en_--
29 | 32
Содержание FN2012-A1
Страница 4: ...4 32 A6V10407862_e_en_ ...