Operating unit with PMI & mainboard FCM2027
11
Technical data
87
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
S33: Switch for ground fault monitoring of the Ethernet connection
S33
Position
Function
Off
Default setting
Setting for networking via FCnet
On
Setting for networking via Ethernet
S38: Switch for ground fault monitoring of the system supply
S38 deactivates the station's internal ground fault monitoring including the
Ethernet interface, which can also be deactivated with S33.
Electrically isolated components, such as the network module (SAFEDLINK),
RS485 module, or optional line cards have their own monitoring and are not
included in the deactivation of ground fault monitoring.
S38
Position
Function
On
Ground fault monitoring activated
Off
Ground fault monitoring deactivated
NOTICE
Information
If an operating unit is integrated in the FC2080 or in the FG2020-D1, then the
ground fault monitoring of the system supply must be deactivated on the PMI &
mainboard FCM2027 (S38 to OFF).
11.5
Technical data
Supply input
Voltage
DV 20…30 V
Quiescent current (display illumination off) 120 mA
Maximum current (display illumination on
and lamp test on)
200 mA
Display
Dimensions (L x W)
115 x 50 mm
Resolution
256 x 112 pixels
Interfaces
3 x slots for serial modules
For RS232 module for event printer
For RS485 module for ESPA-4.4.4
interface, FAT, FBF, UGA or remote
EVAC-NL operation
Connection module (card cage)
2 x slots for network modules
(SAFEDLINK)
Full functionality (incl. degraded mode
function)
Degraded mode function only
1 x Ethernet connection RJ45
10/100 Mbit/s
2 x connections for peripheral data bus
X3, X400
Mechanical data
Dimensions (W x H x D)
427 x 200 x 25 mm
Weight (without options)
1700 g