Periphery board (4 loops) FCI2004-A1
8
Adjustment elements
73
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
8.5
Adjustment elements
Switch
Function
Position
Meaning
S100
Switchover of the indication for the
I/O LEDs (see also H109)
Switchover STATUS indication
DIRECTION indication
8.6
Technical data
Supply input
Designation
'VSYS+'; 'VSYS-'
Operating voltage
DC 21…28.6 V (= Vsys)
Operating current
Max. 5 A
Input
3rd supply source
Designation
'3SRC+'; '3SRC-'
Voltage
DC 7…30 V
Current
Max. 40 mA
Supply outputs 1 and 2
Designation
'VSYS_01', 'VSYS_02'; 'GND'
Voltage
DC 21…28.6 V
Current
Max. 1 A (protected with 1 AT)
Detector lines
Designation
''; 'LOOP1_1-' …
''; 'LOOP2_2-'
Output voltage
Max. DC 33 V
Number of integrated line cards
2
Output current per integrated line card
Max. 0.5 A
Addressable devices per integrated line card Max. 252
Connectable lines per integrated line card
2 loops or 4 stubs (mixed variants are
possible)
Protocol
FDnet
Cable types
All types (recommended: twisted); for
detailed specifications see document
008843
Monitored for
Ground fault
Short-circuit
Open line
Line capacitance
Design
Short-circuit-proof
Voltage surge protection
Open line
Changeover contacts
RT fault
Designation
’FAU_NO’; ’FAU_COM’; ’FAU_NC’
Design
Relay output
Break or make contact
Failsafe
Activated in degraded mode
Switching voltage
Max. DC 60 V
Switching current
Max. 400 mA