![Siemens FibroLaser III Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/siemens/fibrolaser-iii/fibrolaser-iii_maintenance-and-repair_380624009.webp)
Safety
9
Building Technologies
FL-III Maintenance and Repair
CPS Fire Safety
08.2012
2.5
Application specific safety
During the commissioning and testing of the FibroLaser III it must be ensured that:
erroneous triggering of transmission devices is prevented in a reliable manner,
the fire brigade is informed before test triggering of transmission devices,
the triggering of fire extinguishing controls is prevented,
the responsible person is present when third party devices are triggered,
the collective fault output of the controller is connected to the alarm control
system,
the collective alarm output of the controller is connected to the alarm control
system, and
a programmable output is assigned to the test mode and connected to the alarm
control system if the test mode shall be used.
WARNING!
A safe distance from high voltage lines must be maintained in
railway tunnels with electrical traction lines.
Only splice boxes with grounding may be used for metal
containing optical fibre sensor cables. Alternatively, metal-free
sensor cables may be used without grounding.