![Siemens FibroLaser III Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/siemens/fibrolaser-iii/fibrolaser-iii_maintenance-and-repair_380624017.webp)
Maintenance
17
Building Technologies
FL-III Maintenance and Repair
CPS Fire Safety
08.2012
Cleaning the fibre-optical connectors
In order to clean the contaminated endface of a fibre-optical connector, the
protective flap of the connector must be opened carefully. Use a service adapter
E2000 to open the protective flap.
1
Lightly moisten a suitable lint-free cleaning cloth with an ultra-pure solvent.
2
Carefully wipe the surface with the moist cleaning cloth. While doing this,
avoid touching the endface or the sections of the cleaning cloth that have
been used for the cleaning of the parts.
3
Following the successful cleaning, wipe off the surface of the ferrule with a dry
section of the cleaning cloth in order to fully remove any solvent residue.
4
Subsequently check the surface with the microscope.
5
Insert the cleaned and intact fibre-optical connector into the corresponding
fibre-optical port of the controller.
6
Switch the controller on and check the corresponding channel with the “Quick
Start” feature of the software FibroManager. If the message “CHECK
CONNECTOR” is displayed, switch the controller off and repeat the cleaning
procedure of the fibre-optical connector. If this does not lead to the desired
result, then the cleaning of the internal connector is required. In this case, the
fibre-optical connector of the sensor cable must also be cleaned again before
performing the reconnection procedure.
3.3.3
Cleaning the internal fibre-optical connectors
Cleaning the internal fibre-optical connectors with a ferrule cleaner
The corresponding internal fibre-optical connector must be cleaned when the
message “CHECK CONNECTOR” is displayed while checking this channel with
the “Quick Start” feature of the software FibroManager and this message is
displayed repeatedly during the re-checking of the channel, even after repeated
and thorough cleaning of the exterior fibre-optical connector.
The opening of the controller housing via the housing cover is not required for
the cleaning of the internal fibre-optical connectors with a ferrule cleaner
.
The cleaning of the internal fibre-optical connectors of the controller is possible
without requiring the opening of the controller housing by using a ferrule cleaner.
The ferrule cleaner is an optional tool for the cleaning of fibre-optical connectors.
The fibre-optical connectors can be cleaned while they are installed in a mating
adapter.
The instructions of the manufacturer as specified in the documentation of the
respective ferrule cleaner must be observed during the cleaning of the internal
fibre-optical connectors. It is recommended to press the feed button of the ferrule
cleaner three to five times.