Structure and function
3
Function
23
Building Technologies
A6V10227635_g_en_--
Fire Safety
2015-03-11
3.3.6 Test mode
In test mode the radio fire detectors react faster and with a higher sensitivity level.
For testing purposes, the radio fire detectors can be set to test mode using the
control panel or the FXS2061 SWING tool.
The following tests can be performed:
l
Test of optical detector function using test gas
l
Test of heat detector function using hot air
You will find more detailed information in the fire detection system documentation.
3.3.7 Degraded mode in the FDnet/C-NET
When the main processor of the fire control panel fails, the control panel is in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.
l
There are no restrictions on the function of the detector when it is in degraded
mode operation.
l
Degraded mode operation does not affect radio cell communication.
l
A fault message is transmitted to the fire control panel via the radio gateway.
The fire control panels support degraded mode operation in different ways.
During planning, therefore, you must observe the information in the 'List of
compatibility' document and the fire control panel documentation. See the
7]' chapter.
You will find more detailed information in the fire detection system documentation.
3.3.8 Interface to service devices
The fire control panel or the software FXS2061 SWING tool is used to read out and
set the parameter sets.
The detector exchanger and tester FDUD292 and the intelligent detector tester
FDUD293 cannot be used to read out or set the parameter sets.