4BMounting / Installation
34BPreparing detector base FDB22x for installing an FDOOT241-A3 or FDOOT241-A4
5
75 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
5.4
Preparing detector base FDB22x for installing an
FDOOT241-A3 or FDOOT241-A4
The point detectors FDOOT241-A3 and FDOOT241-A4 can be used to replace
detectors from the AnalogPLUS or SIGMALOOP detector families.
You will find details in the 'List of compatibility'.
Use one of the FDB221, FDB221-AA, or FDB222 detector bases.
1.
Use the table below to determine the resistance which corresponds to the
existing detector type.
Resistor connection
R = ∞Ω
Do not install a resistor
2.
Install the resistor. See figure 'Resistor connection'.
–
If the detector is replacing a DO1131A, SDF1200, or SDF2200, do not
install a resistor.
3.
Use the auxiliary terminal DBZ1190-AA for multiple assignment. See figure
'Resistor connection'.
D 113 A
T
2
DO 1131A
T
DT1131A
SDF 00
31
SDT2100
+
-
+
-
+
-
R
DO113 A
1
R = Ω
+
R = 10 kΩ ±2 kΩ (0,25 W)
R = 18 kΩ ±2 kΩ (0,25 W)
R = 27 kΩ ±2 kΩ (0,25 W)
1