Commissioning
Checking function
6
49 | 62
Building Technologies
009757_f_en_--
Fire Safety
2016-08-23
6.2 Checking function
The manual call point is installed and electrically connected.
1. Set the detector line to 'Test' on the control panel.
2. Insert the key into the housing from below, as shown in the diagram.
The glass insert or plastic insert falls down and activates the alarm actuator
in the switching unit.
The LED flashes.
3. Pull off the key.
The glass insert or plastic insert is pushed back into its original position.
The manual call point is ready for operation again.
4. Set the detector line to 'Normal operation' on the control panel.
The detector line is ready for operation again.
Figure 26: Testing the manual call point FDM221 with the key
FDM225
FDM226
FDM221
1
3
2