Siemens FDK:085U0226 Скачать руководство пользователя страница 1

SITRANS F

Communication Modules

Add-on modules
HART

Operating Instructions • 07/2010

Содержание FDK:085U0226

Страница 1: ...SITRANS F Communication Modules Add on modules HART Operating Instructions 07 2010 ...

Страница 2: ......

Страница 3: ... explanation 9 4 6 2 Sensorprom 9 5 Device Variables 9 6 Dynamic Variables 9 6 1 MAG 5000 C 6000 9 6 2 MASS 6000 9 7 Status Information 10 7 1 Device status 10 7 2 Extended device status 10 7 3 Additional device status Command 48 10 8 Universal Commands 11 9 Common Practice Commands 12 10 Device Specific Commands 13 11 Tables 17 11 1 Volume flow unit codes 17 11 2 Volume unit codes 18 11 3 Mass fl...

Страница 4: ...r is familiar with HART Protocol requirements and terminology AOM Add On Module USMII Concept with flexible plug play fieldbus modules SensorProm Storing unit for all settings HCF HART communication foundation FSK Frequency Shift Keying physical layer CN Capacitance number capacitance as a multiple of 5000 pF pF Picofarad 10 12 Farad unit of electrical capacitance PV Primary variable SV Secondary ...

Страница 5: ... is based on the flexible USM II technology This includes the AOM Add On Module that provides digital communications capabilities for the USM II transmitters This approach gives far more flexibility and greater long term protection of your signal converter investment than is possible with factory standard off the shelf signal converter designs With this easy to use system providing additional func...

Страница 6: ...le The installation procedure for the HART module is as follows 4 2 Mechanical Installation MAG MASS 6000 4 Product interfaces 1 Unpack the add on module and insert it in the bottom of the signal converter as shown 19 rack mounted versions IP 67 compact versions This completes the add on module installation and the signal converter may now be connected to the terminal box Communication with the di...

Страница 7: ...nections must be made Terminal 31 must be connected to 91 and terminal 32 must be connected to 92 Electrical wirering can be seen in the drawing below 4 5 Current output A true HART signal consists of a Current output combined with a HART FSK signal In order to achieve this connections must be made according to the chapter HART electrical connections When a HART module is installed the Current out...

Страница 8: ...ll remain Temperature Massflow Fraction A Fraction B Pct Fraction A OFF The Current output is deactivated The Current output is forced to 3 mA to indicate a Warning Current output mode 0 20 mA Not possible 0 mA can cause HART masters to stop communicating or report errors This is because values below 4mA are used for alarms and validation of the current loop 4 20 mA Factory setting 4 20 mA Alarm F...

Страница 9: ...d display 1 Press Top key for two seconds NOTE For View mode only skip steps 2 3 2 Type in password 1000 by pressing Change key two times and then press Lock key and wait for two seconds 3 The display now says Basic settings 4 Press Forward key until you reach the HART module menu item 5 Press Lock key 6 You can now cycle through all the HART settings by pressing Forward key 7 Press Top key for tw...

Страница 10: ...to other than the specified PV SV TV and QV 6 1 MAG 5000 C 6000 Item Value Description HART 0 15 Device address Factory setting 00 short address TAG name 8 characters Can be used to TAG the device TAG descriptor 16 characters Can be used to describe the TAG TAG date 3 bytes Can be used to date the installation HART x xx Firmware version of the HART module SW version 6 2 MASS 6000 Meaning Units PV ...

Страница 11: ... overflow warning error no 30 is pending This chapter defines all status provided by the flowmeter including the Device status byte the Extended Device Status byte and status information returned in Command 48 7 Status Information 7 1 Device status 7 2 Extended device status The extended device status bits are not supported by the flowmeter Value is always zero 7 3 Additional device status Command...

Страница 12: ...in command 11 Read unique id Byte 0 5 As Command 0 associated with tag TAG 8 characters 12 Read message None Byte 0 23 Message 13 Read Tag Descriptor None Byte 0 5 Tag Date Byte 6 17 descriptor Byte 18 20 date 14 Read PV sensor number None Byte 0 2 sensor serial number Byte 3 unit code for sensor limits and min span Byte 4 7 upper sensor limit Byte 8 11 lower sensor limit Byte 12 15 minimumspan 15...

Страница 13: ...ys 4 mA 41 Perform transmitter Not implemented self test 42 Perform master reset None None Set to default Busy for approx 30 seconds after reply 43 Set PV zero None None HART will respond command not implemented in the cases that PV zero is not supported by the application 44 Write PV units Byte 0 PV units code As in command 45 Trim DAC Zero Not implemented 46 Trim DAC gain Not implemented 47 Writ...

Страница 14: ...te 0 3 Four bytes Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 4 Index 134 Read Float32 Byte 0 CANAPP ID Byte 0 3 Float Byte 1 Attribute ID Byte 2 Attribute Qual Comment When reading values Byte 3 Unit code with no unit the unit code must Byte 4 5 Index be 251 No unit 135 Read Float64 Byte 0 CANAPP ID Byte 0 7 Float 64 Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 4 Index 136 Read VisibleSt...

Страница 15: ...Qual Byte 3 Reserved 0x00 Byte 4 5 Index 2 bytes Bytes 6 7 Unsign16 146 Write Unsigned32 Byte 0 CANAPP ID Byte 0 3 Four bytes Byte 1 Attribute ID Byte 2 Attribute Qual Byte 3 Reserved 0x00 Byte 4 5 Index 2 bytes Byte 6 9 Unsign32 147 Write VisibleString Byte 0 CANAPP ID Byte 0 Length of Message Byte 1 Attribute ID Byte 1 x User message Byte 2 Attribute Qual 32 bytes Byte 3 Reserved 0x00 Byte 4 5 I...

Страница 16: ...toutput1 Byte 0 0 Off As command MASS 6000 only 1 Massflow 2 Fraction A 3 Fraction B 4 Volumeflow 5 Sensor temperature 6 Density 7 Pct Fraction A 181 Read Currentoutput1 None Byte 0 0 Off MASS 6000 only 1 Massflow 2 Fraction A 3 Fraction B 4 Volumeflow 5 Sensor temperature 6 Density 7 Pct Fraction A 182 Write Digitaloutput1 Byte 0 0 Off As command 1 Pulse 2 Frequency 3 Error level 4 Error number 5...

Страница 17: ...izer reset 6 Force output 7 Freeze output 8 Qmax 2 night 9 Manual Cleaning MASS 6000 Byte 0 0 Off 1 Start Batch 2 Hold continue Batch 3 Stop Batch 4 Zero Adjust 5 Totalizer reset 6 Force output 7 Freeze output 187 Read Digitalinput1 None MAG 5000 C 6000 Byte 0 0 Off 1 Start Batch 2 Hold continue Batch 3 Stop Batch 4 Zero Adjust 5 Totalizer reset 6 Force output 7 Freeze output 8 Qmax 2 night 9 Manu...

Страница 18: ...per second 29 Cubic meters per day 30 UK gallons per hour 31 UK gallons per day 122 Normal liters per hour Same as l h 130 Cubic feet per hour 131 Cubic meters per minute 136 US gallons per hour 137 UK gallons per second 138 Liters per hour 235 US gallons per day 240 Milli liters per second 241 Milli liters per minute 242 Milli liters per hour 243 Hector liters per second 244 Hecto liters per minu...

Страница 19: ...cond 71 Grams per minute 72 Grams per hour 73 Kilograms per second 74 Kilograms per minute 75 Kilograms per hour 76 Kilograms per day 77 Metric tons per minute 78 Metric tons per hour 79 Metric tons per day 80 Pounds per second 81 Pounds per minute 82 Pounds per hour 83 Pounds per day 84 Short tons per minute 85 Short tons per hour 86 Short tons per day 87 Long tons per hour 88 Long tons per day 2...

Страница 20: ... Bits of additional device status 76 bits informational 25 bytes in total Alternative operating modes No Burst Mode Yes Write protect No 12 Performance 12 1 Sampling rates MAG 5000 C 6000 PV digital calculation Volume flow Equals the Excitation frequency SV digital calculation Totalizer 1 2 per second TV digital calculation Totalizer 2 Batch 2 per second Analog output update Equals the Excitation ...

Страница 21: ... Siemens A S Flow Instruments Nordborgvej 81 DK 6430 Nordborg Subject to change without prior notice Order No A5E03089708 Lit No A5E03089708 01 SFIDK PS 023 F2 02 Siemens AG 07 2010 For more information www siemens com flow A5E03089708 ...