3
Structure and function
Function
36
Building Technologies
A6V10334410_h_en_--
Fire Safety
2015-09-29
3.5.1.3
Test mode
For testing purposes the aspirating smoke detectors can be set to test mode. Test
mode does the following:
The relays are deactivated.
The buzzer is operated at a lower sound level.
The green operating indicator
flashes.
No changes are made to the sensitivity.
Electronic testing:
The aspirating smoke detectors can be tested on FC20xx/FC72x fire control panels
(market package MP5.0/IP5 or higher) using detector exchanger and tester
FDUD292 or intelligent detector tester FDUD293.
You will find more information in documents 007227 and 009718.
See also
3.5.1.4
Renovation mode
When operating the point detectors on the FDnet/C-NET, individual detectors can
be set specifically to renovation mode on the fire control panel.
Select renovation mode if major work is being carried out in the room and large
volumes of dust or aerosols are being produced.
In renovation mode, the detector is operated with the least sensitive parameter set
(no. 10).
See also
3.5.1.5
Line separator
Line separators are electronic switches which isolate the defective part in case of a
short-circuit on the FDnet/C-NET detector line. The rest of the detector line remains
serviceable. On a loop line all FDnet/C-NET devices remain fully functional after a
simple error.
The function of the line separator is integrated in communication transponder
FDCC221S.
See also
Communication transponder FDCC221S [➙
3.5.1.6
Line tester FDUL221
The line tester FDUL221 detects aspirating smoke detectors on the FDnet/C-NET
detector line.
You will find more information in document 008250.
See also