Appendix E: Device type list
19
138 | 151
A6V10421795_en--_k
19 Appendix E: Device type list
You can number devices freely from 1 to 400 and assign them to the following
zones:
● Zone (T1…T8): used for devices of Technical, Tech. latched, Fault and Gas
types.
● Zone (1…32): used for devices of Auto alarm, Manual alarm and Sprinkler
types.
Device types
Parameters
Values
Optional
zone
Optional devices
Auto alarm Dev.
AVC function
ON (default)
Zone 1…32
FDF241-9, FDL241-9, HI722, HI720,
OH720, OOH740, OP720, OP360, HI360,
OH360; Fire sensor on OOHC740;
Collective input on FDCI723; General
input on FDCI221, FDCI361, FDCIO221,
FDCI222, FDCIO222, FDCIO224,
FDCIO361
OFF
Type A
function
ON
OFF
(default)
Type A inhibit
time(sec)
30…60
60 (default)
Latched
Yes
(checked,
default)
Yes
(unchecked)
Manual alarm
AVC function
ON
Zone 1…32
FDM221, FDM223, FDM224, FDM225,
FDM226, FDM231, FDM365-RP;
Collective input on FDCI723; General
input on FDCI221, FDCI361, FDCIO221,
FDCI222, FDCIO222, FDCIO224,
FDCIO361
OFF
(default)
Sprinkler Dev.
-
-
Zone 1…32
General input on FDCI221, FDCI361,
FDCIO221, FDCI222, FDCIO222,
FDCIO224, FDCIO361
Technical Dev.
Technical
device with
panel buzzer
activation
-
Zone T1…T8 General input on FDCI221, FDCI361,
FDCIO221, FDCI222, FDCIO222,
FDCIO224, FDCIO361
Tech. latched
Technical
Latched
device with
panel buzzer
activation
-
Zone T1…T8 General input on FDCI221, FDCI361,
FDCIO221, FDCI222, FDCIO222,
FDCIO224, FDCIO361
Gas Dev.
-
-
Zo
ne T1…T8 CO sensor on the OOHC740
Fault Dev.
-
-
Zone T1…T8 General input on FDCI221, FDCI361,
FDCIO221, FDCI222, FDCIO222,
FDCIO224, FDCIO361