Validity of the documentation

This equipment manual describes the following products:

 System family

Product

Article number

SIMATIC Distributed I/O System ET 200SP 
HA

IM 155-6 PN HA

6DL1155-6AU00-0PM0

SIMATIC Distributed I/O System ET 200SP 
HA

IM 155-6 PN HA

6DL1155-6AU00-0EM0

SIMATIC Distributed I/O System ET 200SP 
HA

BA 2x RJ45

6DL1193-6AR00-0AA0

SIMATIC Distributed I/O System ET 200SP 
HA

BA 2xLC

6DL1193-6AG00-0AA0

SIMATIC Distributed I/O System ET 200SP 
HA

BA 2xFC

6DL1193-6AF00-0AA0

SIMATIC Distributed I/O System ET 200SP 
HA

BA LC/RJ45

6DL1193-6AG20-0AA0

SIMATIC Distributed I/O System ET 200SP 
HA

BA LC/FC

6DL1193-6AG40-0AA0

It supplements the system manual of the ET 200SP HA Distributed I/O System

Functions that generally relate to the system are described in this manual.

The information in this product manual, system manual and function manual enables you to 
commission the ET 200SP HA distributed I/O system.

Conventions

Please also observe notes marked as follows:

Note

A note contains important information on the product described in the documentation, on the 
handling of the product, or on the section of the documentation to which particular attention 
should be paid.

Changes compared with the previous version

You can find an overview of the most important changes in this documentation:

As of document version AE: 
Supplement for the use of fail-safe I/O modules in distributed I/O devices.

IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE

7

Содержание ET 200SP HA

Страница 1: ...1193 6AG20 0AA0 6DL1193 6AG40 0AA0 6DL1193 6AF00 0AA0 6DL1155 6AU00 0PM0 6DL1155 6AU00 0EM0 09 2021 A5E39262148 AE Security information 1 Preface 2 Product overview 3 Terminal 4 Parameters 5 Behavior of the device name 6 Displays and interrupts 7 Technical specifications 8 Diagnostic messages A ...

Страница 2: ...nnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers are...

Страница 3: ...17 3 4 6 Access types 17 3 4 7 Overview of access types 18 3 4 7 1 Full access 18 3 4 7 2 No access 18 3 5 Configuration limit for IO devices 19 3 5 1 Maximum number of connections to IO controllers 19 3 5 2 Maximum permissible bytes 19 4 Terminal 21 4 1 24 V DC supply voltage 21 4 2 Schematic circuit diagram 22 5 Parameters 23 6 Behavior of the device name 25 7 Displays and interrupts 27 7 1 Stat...

Страница 4: ...ions 35 A Diagnostic messages 45 A 1 Diagnostics alarms 45 A 2 Maintenance events 46 A 3 Diagnostics of a shared device 47 Tables Table A 1 Diagnostic messages their meaning and possible remedies 45 Table A 2 Maintenance messages their meaning and possible remedies 47 Table of contents IM 155 6 PN HA 4 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 5: ... the Internet if and only to the extent necessary and with appropriate security measures firewalls and or network segmentation in place You can find more information on protective measures in the area of industrial security by visiting https www siemens com industrialsecurity Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recommends performi...

Страница 6: ...Security information IM 155 6 PN HA 6 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 7: ...AG40 0AA0 It supplements the system manual of the ET 200SP HA Distributed I O System Functions that generally relate to the system are described in this manual The information in this product manual system manual and function manual enables you to commission the ET 200SP HA distributed I O system Conventions Please also observe notes marked as follows Note A note contains important information on ...

Страница 8: ...Preface IM 155 6 PN HA 8 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 9: ... status QI Multi Hot Swap pulling plugging of multiple I O modules during operation Saving service data Recording the value status of I O modules Reference temperature distribution Note The IM 155 6 PN HA cannot be pulled plugged when the associated connector for the supply voltage is plugged in In addition to the technical specifications this module supports the following PROFINET IO functions Su...

Страница 10: ...Article number LED for maintenance Connector for supply voltage 2D matrix code Slot for PROFINET BusAdapter LED for master operation PROFINET BusAdapter LED for supply voltage Terminal block for interface module figure for redundant interface modules 3 2 Accessories Definition Accessories for the interface module must be ordered separately Product overview 3 2 Accessories IM 155 6 PN HA 10 Equipme...

Страница 11: ... Connect bus cable BA2xRJ45VDHA 6GK5 991 2VA00 8AA2 Adapter for connection of an IO device to the PROFI NET IO system using a 2 wire system with copper wires Carrier modules Carrier for one IM 155 6 PN HA Carrier for two IM 155 6 PN HA for redundant configuration Server module Power bus cover Labeling strips Reference identification label 3 3 Fail safe I O modules in the I O device 3 3 1 Response ...

Страница 12: ...llers to the individual submodules is ensured Shared device in different projects The stations with the IO controllers that use the shared device are created in different projects It must be ensured in each project that the shared device has the exact same configuration in each station Only one IO controller may have full access to a submodule at any given time The IP parameters and device names m...

Страница 13: ...ave the hardware configuration and close the configured station 5 Open the other previously created station in the hardware configuration in the configuration tool 6 Add the IO device as shared device 7 Save and compile the hardware configuration and close the hardware configuration in the configuration tool and the project Result The shared device is created You assign the submodules to the confi...

Страница 14: ...he hardware configuration in the configuration tool and configure the CPU with PROFINET interface a SIMATIC S7 410 5H in the described case 4 Assign parameters to the PROFINET interface of the station created 5 Save and compile the station and close the project 6 Create another project with the name Shared Device 2 in the configuration tool 7 Add a station e g SIMATIC S7 417 with the name CPU2 8 R...

Страница 15: ...at changes to one station affect other station s Note Access rules A submodule may only be assigned to one IO controller at any given time in the hardware configuration in the configuration tool This means that the submodule in slot 4 for example can only be assigned to the CPU1 with the setting full access in CPU2 the setting for the submodule in slot 4 must therefore be corresponds to no access ...

Страница 16: ... 1 to 5 for the project Shared device 2 with CPU2 7 Download the configuration to the stations Note Changing projects Note that changes to a shared device e g at the interface or port must always be made in all projects in which the shared device is being used The projects must subsequently be compiled and downloaded Shared device in the user program The shared device has no special role in the us...

Страница 17: ...n allows you to split submodules of an IO device between different IO controllers Data from sensors in close proximity can be passed to different IO controllers Description Access to the submodules of the shared device is distributed among the individual IO controllers Each submodule of the shared device can be assigned exclusively to one IO controller When a shared device is configured on a redun...

Страница 18: ...a output data and data records Parameter assignment of the submodule Receiving alarms of the submodule 3 4 7 2 No access Definition The IO controller does not have access to the submodule and the submodule therefore has no logical address Description The following functions are not available for the IO controller Data exchange is not possible with the submodule Alarms of the submodule cannot be re...

Страница 19: ...tes in the output data area Connection type Number of IO controllers with connection to the shared de vice Requirement for the input data or out put data Without system redun dancy 1 IO controller Maximum of 1440 bytes each 2 IO controllers Maximum of 1440 bytes for each control ler 3 or 4 IO controllers Maximum of 360 bytes each System redundancy S2 1 redundant IO controller Maximum of 1000 bytes...

Страница 20: ...Product overview 3 5 Configuration limit for IO devices IM 155 6 PN HA 20 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 21: ...4 V DC for looping through 2 1M Ground 2M Ground for looping through 2 1 1L and 2L as well as 1M and 2M are bridged internally 2 Maximum 10 A permitted Note Pin assignment BusAdapter You can find information on pin assignment of the BusAdapter under https support industry siemens com cs ww en view 109773801 https support industry siemens com cs ww en view 109773801 IM 155 6 PN HA Equipment Manual ...

Страница 22: ...witch L Supply voltage 24 V DC Backplane bus connection and electronics M Ground Backplane bus LK 1 2 Link TX RX LED Internal voltage distribution ACT ACT LED X80 Supply voltage infeed 24 V DC RN RUN LED green X5 BusAdapter ER ERROR LED red P1 R PROFINET interface X1 Port 1 MT MAINTENANCE LED yellow P2 R PROFINET interface X1 Port 2 PWR Power LED green Terminal 4 2 Schematic circuit diagram IM 155...

Страница 23: ...rs 5 Definition The parameter assignment specifies the properties of the IO device Description You configure the ET 200SP HA on a CPU 410 as of FW V8 2 IM 155 6 PN HA Equipment Manual 09 2021 A5E39262148 AE 23 ...

Страница 24: ...Parameters IM 155 6 PN HA 24 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 25: ...os are the result of saving the device name on the BusAdapter and in the interface when exchanging the two components Interface non program med without device name Interface with device name BusAdapter non program med without device name No device names When the supply voltage is switched on the device name is copied from the interface to the BusAdapter BusAdapter with device name When the supply ...

Страница 26: ...Behavior of the device name IM 155 6 PN HA 26 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 27: ...splays are status and error indicators Diagnostics messages and maintenance events as well as their possible causes or solutions are described in the diagnostics messages and maintenance events Diagnostics alarms Page 45 IM 155 6 PN HA Equipment Manual 09 2021 A5E39262148 AE 27 ...

Страница 28: ...Page 29 red MT LED Page 30 yellow ACT LED Page 30 green PWR LED Page 31 green On BusAdapter LED LK1 Page 31 green LED LK2 Page 31 green 7 2 LEDs 7 2 1 RN LED Definition The RN LED provides information about the status of the IM Displays and interrupts 7 2 LEDs IM 155 6 PN HA 28 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 29: ...he following errors ER LED Meaning Remedy Flashes Group fault and group fault for chan nels Evaluate the diagnostics and eliminate the error Configured settings do not match the actual configuration of the ET 200SP HA Check the configuration of the ET 200SP HA for missing modules de fective modules or the presence of non configured modules Impermissible configuration states You can find informatio...

Страница 30: ...was configured with V1 0 in HW Config and both IMs have different firmware versions the following behavior can occur Maintenance LED and ER LED are illuminated on both IMs The cause can be a firmware update of a redundant interface module IM from V1 0 x to a higher version or replacement of an IM Solution Make sure that both IMs have the same firmware version 7 2 4 ACT LED Definition The ACT LED i...

Страница 31: ... via this IM The partner IM cannot apply the data exchange 7 2 5 PWR LED Definition The PWR LED provides you status information about supply voltage L Description The PWR LED indicates the following status PWR LED Meaning Off Missing supply voltage or insufficient supply voltage at the interface module On Supply voltage L available 7 2 6 LEDs LK1 LK2 on the BusAdapter Definition The LK LEDs on the...

Страница 32: ...or display provides information on the cause of the error The LED error display takes precedence over all other states that are displayed by the ERROR and MAINT LEDs remains switched on until the cause of the error is eliminated Error type and error location display Page 32 Example for error display Page 33 Displaying unsupported bus adapters The LEDs RN flashing ER flashing and MAINT off on the i...

Страница 33: ...n eliminated 7 4 2 Example for error display Example Error type MAINT Error code Cause of error Solution 1 65 No server module Interruptions on the backplane bus Short circuit on backplane bus Check the configuration of the ET 200SP HA Note The following LEDs indicate a short circuit in the backplane bus supply or in the bus connection supply LED PWR On LED RN ER and MT Off 7 5 LED display for set...

Страница 34: ... real slot Failure of redundancy partner Impermissible bus adapter on interface module Incorrect bus adapter in redundancy partner Permissible backplane bus size exceeded No server module Diagnostics of I O modules are forwarded by the IM 155 6 PN HA and depend on the respective I O module The IM 155 6 PN HA generates a maintenance message for the following events Different hardware firmware in th...

Страница 35: ...ed integrated from version V3 0 Configuration control via dataset No Supply voltage Rated value DC 24 V permissible range lower limit DC 19 2 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Short circuit protection Yes Mains buffering Mains voltage failure stored energy time 10 ms Input current Current consumption max 700 mA 19 2 V to 28 8 V DC Inrush current max 5 A I t ...

Страница 36: ...ter integrated switch Yes BusAdapter PROFINET Yes Compatible BusAdapters BA 2x RJ45 BA 2x FC BA 2x LC BA LC RJ45 BA LC FC BA VD Protocols PROFINET IO Device Yes Open IE communication Yes Media redundancy Yes as MRP client Interface types RJ 45 Ethernet Transmission procedure PROFINET with 100 Mbit s full duplex 100BASE TX 100 Mbps Yes PROFINET with 100 Mbit s full duplex 100BASE TX Autonegotiation...

Страница 37: ...d with 1 500 V DC Permissible potential difference between different circuits Safety extra low voltage SELV Isolation Isolation tested with 1 500 V DC 1 min type test Ambient conditions Ambient temperature during operation horizontal installation min 40 C horizontal installation max 70 C vertical installation min 40 C vertical installation max 60 C Dimensions Width 50 mm Height 138 mm Depth 89 mm ...

Страница 38: ...current max 5 A I t 0 36 A s Due to increased mains buffering of 10 ms Power Infeed power to the backplane bus 7 5 W no doubling in redundant mode as the in feed power is also designed as redundant Address area Address space per module Address space per module max 256 byte Hardware configuration Integrated power supply Yes 24 V DC Rack Modules per rack max 56 56 slots for I O modules server module...

Страница 39: ...nction Yes Diagnostics indication LED RUN LED Yes green LED ERROR LED Yes red LED MAINT LED Yes Yellow LED ACT LED Yes green LED Monitoring of the supply voltage PWR LED Yes green PWR LED Connection display LINK TX RX Yes 2x green link LEDs on BusAdapter Potential separation between PROFINET and all other circuits Yes 1 500 V AC Permissible potential difference between different circuits Safety ex...

Страница 40: ...he manuals of the I O modules Article number 6DL1193 6AR00 0AA0 General information Product type designation BA 2x RJ45 Interfaces Number of PROFINET interfaces 1 2 ports switch RJ45 Supports protocol for PROFINET IO Number of RJ45 ports 2 Cable length Cu conductors 100 m Ambient conditions Ambient temperature during operation min 40 C max 70 C Dimensions Width 20 mm Height 69 5 mm Depth 59 mm Wei...

Страница 41: ...e graded index fiber 62 5 125 μm 3 km Ambient conditions Ambient temperature during operation min 40 C max 65 C redundant design 2x 6DL1155 6AU00 0PM0 max 60 C horizontal max 50 C vertical When using different I O devi ces the derating specified there must be observed Dimensions Width 20 mm Height 75 mm Without protective caps approx 8 mm Depth 59 mm Weights Weight approx 60 g Technical specificat...

Страница 42: ...protocol for PROFINET IO Number of FC FastConnect connections 2 Cable length Cu conductors 100 m Ambient conditions Ambient temperature during operation min 40 C max 70 C Dimensions Width 20 mm Height 69 5 mm Depth 59 mm Weights Weight approx 53 g Technical specifications 8 1 Technical specifications IM 155 6 PN HA 42 Equipment Manual 09 2021 A5E39262148 AE ...

Страница 43: ...3 km Standards approvals certificates RoHS conformity Yes China RoHS compliance Yes Ambient conditions Ambient temperature during operation min 40 C max 70 C Tmax for horizontal installation for vertical installation Tmax 60 C redundant setup 2x 6DL1155 6AU00 0PM0 max 65 C horizontally max 60 C vertically When using different IO De vices the derating specified there must be ob served Dimensions Wi...

Страница 44: ...25 μm 3 km Standards approvals certificates RoHS conformity Yes China RoHS compliance Yes Ambient conditions Ambient temperature during operation min 40 C max 65 C Tmax for horizontal installation for vertical installation Tmax 60 C redundant setup 2x 6DL1155 6AU00 0PM0 max 60 C horizontally max 55 C vertically When using different IO De vices the derating specified there must be ob served Dimensi...

Страница 45: ...ermi nal block is installed Configuration error Permissible back plane bus size excee ded 0x0602 0x0698 Configura tion The total width of the instal led modules exceeds the per missible assembly length of 1300 mm Verify that the backplane bus configuration does not exceed the permissible size The server module must be the last module plugged in high est permissible slot number 58 Configuration err...

Страница 46: ...ncy partners have different hard ware firmware 0x0630 0x06D3 Redundant modules The redundant modules dif fer in terms of the hardware or firmware versions Make sure that the hardware or firmware versions of the re dundant modules are identi cal Hardware version Replace at least one mod ule Firmware version Perform a firmware update PROFINET IO Another source of diagnostic events is the PROFINET ba...

Страница 47: ...3 Diagnostics of a shared device The configuration prevents direct diagnostics of a shared device or shared module Recommendation for naming I O components When the I O components are located in a different AS you should note the following Specify the name for I O components so that messages point directly to the shared components Diagnostics of a shared device If commissioning is not possible or ...

Страница 48: ...Diagnostic messages A 3 Diagnostics of a shared device IM 155 6 PN HA 48 Equipment Manual 09 2021 A5E39262148 AE ...