Fault Handling
ECOFAST Motor Starters
5-4
GWA 4NEB 950 5221-12 DS 01
5.2
Potential Faults in Motor Starters with PROFIBUS-DP
Motor starter: 3RK1303-2AS54-1AA.
Table 5-1: Faults and fault handling for 3RK1 303-5BS44-1AA.
Potential faults
Action
LED
indicator
Acknow-
ledged by
Comment
Bus fault
Switch substi-
tute value
AS-i: red
Auto
*)
Check the communication con-
nection to the field bus master.
Possible causes of faults:
• Bus line severed
• Field bus master defective
Process image
error
Trip
SF: red
OFF
command
Deactivate the Motor CW/CCW
control command.
Undervoltage
AS-i
Trip
SF: red
Auto
*)
Check the power supply.
U
DC24V-NS
< 18 V
Undervoltage
AUX PWR
Trip
SF: red
Auto
*)
Check the power supply.
U
DC24V-S
< 18 V
No main power
supply
Fault not recognized!
If the motor cannot be switched
on even though it is properly
connected and power has been
applied, the internal fuses are
defective.
−>
Replace the device!
Sensor supply
overload
Trip
SF: red
Trip reset
Check the sensor supply.
I
Sensor
> 200 mA
Temperature
sensor
overload
Warning/
SF: red
Auto
*)
Wait until the motor has cooled
down.
Trip
SF: red
Autoreset/
trip reset
Wait until the motor has cooled
down.
Acknowledge after motor has
cooled down.
If acknowledgement is not possi-
ble, the motor is still too hot.
Temperature
sensor
short-circuit
Warning/
SF: red
Auto
*)
Remove the short-circuit on the
temperature sensor lead.
Trip
SF: red
Autoreset/
trip reset
Remove the short-circuit on the
temperature sensor lead.
Acknowledge once the fault has
been rectified.
Temperature
sensor
wire break
Warning/
SF: red
Auto
*)
Remove the wire break on the
temperature sensor lead.
Trip
SF: red
Autoreset/
trip reset
Remove the wire break on the
temperature sensor lead.
Acknowledge once the fault has
been rectified.
Self-test fault
(device fault)
Trip
SF: red
Power OFF
Switch the device off and then
back on.
Switching ele-
ment defective
Trip
SF: red
STATE: red
Power OFF
If a device fault is reported
again, the device must be repla-
ced.
*
Once the cause of the fault has been removed, the fault is acknowledged automatically regardless
of the parameters set (not to be confused with autoreset).
Содержание Ecofast 3RK1 323-2AS54-1AA0
Страница 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Страница 2: ......
Страница 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Страница 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Страница 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Страница 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Страница 75: ......