Fault Handling
ECOFAST Motor Starters
GWA 4NEB 950 5221-12 DS 01
5-3
Deutsc
h
En
glish
5.1.1
Acknowledging Faults
Switch-on after device-internal trip
If the motor starter trips the switching elements automatically, it will not
switch on again until
• the cause of the fault has been removed
• the fault has been acknowledged
Acknowledgement
You can acknowledge faults as follows:
• With "trip reset"
– Bit DO-0.3
"trip reset" via field bus
• With a countercommand (e.g. "Motor off" (process image errors only))
• Automatic acknowledgement depending on the PO-0.3 "Autoreset" parameter
(only valid for temperature sensor errors)
Attention
If trip reset is applied constantly, the acknowledgement is triggered once by
edge triggering
If trip reset (output DO-0.3) is applied for longer than 2 seconds and there is
no general fault/general warning present, the self-test function is triggered.
This results in overload tripping with "Warn/Trip", depending on the
"Behavior in the event of overload - temperature sensor" parameter (PO-0.2).
Trigger trip reset (delete signaling bits)
Signal result and enter in
500 ms
> 10 ms
diagnosis buffer
Содержание Ecofast 3RK1 323-2AS54-1AA0
Страница 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Страница 2: ......
Страница 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Страница 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Страница 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Страница 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Страница 75: ......