background image

Siemens Industry, Inc.  

A6V11416604 

2018-07-11  1 / 4 

s

 

 

 
 

 

 

Smoke Control Compliant 
Actuating DXR 

DXR2.E10PL-102BK 
DXR2.E10PLX-102BK 
DXR2.M10PL-102BK 
DXR2.M10PLX-102BK

 

Installation Instruction 

 

Product Numbers

 

Accessories 

985-124 

499 OHM Resistor Assembly Kit 

   

  Smoke Control Compliance 

Parts for Smoke Control Compliance 

Smoke Control Listed Small Equipment 
Controller Enclosure 

540-155K , 
540-155D 

Smoke Control Listed Large Equipment 
Controller Enclosure  

550-002K  

UL Listed Class 2 transformer with 
120Vac 50/60 HZ 0.5A primary with hub 
and 24 Vac 96VA  

TR100VA004  

Smoke Control Compliance  

The following instructions and information apply if used for 

smoke control sequence.  

 

Install Smoke Control Listed products, enclosure and trans-
former (see Parts for Smoke Control Compliance section for 
more information).  

 

Input Rating:  

 

- 24V 60 HZ 72 VA  

 

Digital Output (DO) are the only I/O suitable for smoke con-
trol application. Digital Output (DO) Electrical Ratings:  

 

24 Vac,  6VA per DO/maximum 40 VA total.  

 

Connection from the DXR2 to the field panel is a maximum 
4000 feet, 24 AWG minimum.  

 

Wiring Range:  

 

- Transformer: primary 14 AWG  

 

- 24 Vac Input Power: 14 to 18 AWG  

 

- DO: AI: 18 to 20 AWG  

 

- DI: 18 AWG  

 

- LAN: 20 to 24 AWG  

 

KNX port (11 and 12) not used or connected for smoke 
control application 

All circuits are power limited; FLN is RS-485 or 

Ethernet. 
See the following documents for more information on 

configuring smoke control applications:  

 

Smoke Control Systems Application and Engi-
neering Manual (125-1806)  

 

Smoke Control System Application Guide 
(125-1816)  

 

NFPA and UL Standards Relevant to Smoke 

Control System Application Guide (125-1817) 

 

 

NOTE: 

The 24 Vac relay module is not 

applicable for smoke control 

application. 

 

 

A6V11416604 

Отзывы: