6.3.2
IO redundancy
Definition
You can configure two identical modules redundantly. To do so, plug both modules into a
redundant terminal block side by side. You can find additional information on mounting
modules in an IO redundancy configuration in the ET 200SP HA System Manual, section
"Installing", "Installing terminal block".
In IO redundancy mode, the left module is the master and the right module is the slave.
Description
Both redundant modules measure simultaneously and independently in the process. Both
redundant modules generate diagnostics, interrupts and process values.
6.3.3
Diagnostics, Short-circuit to ground
Definition
Enabling of the diagnostics if a short-circuit of the actuator supply to ground occurs.
6.3.4
Diagnostics, Wire break
Definition
When wire-break check is activated, you can enable wire-break diagnostics via the Diagnostics,
Wire break parameter for insufficient current flow on the input.
6.3.5
Wire-break check
Definition
Enable for wire break check. The I/O module can only detect a wire break if wire-break is
activated.
Parameters
6.3 Explanation of the module/channel parameters
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
21
Содержание DI 16x24VDC HF
Страница 6: ...Security information DI 16x24VDC HA 6 Equipment Manual 10 2020 A5E39265608 AD ...
Страница 8: ...Preface DI 16x24VDC HA 8 Equipment Manual 10 2020 A5E39265608 AD ...
Страница 10: ...2D Matrix code QR code EAN code DI 16x24VDC HA 10 Equipment Manual 10 2020 A5E39265608 AD ...
Страница 18: ...Terminal 5 5 Schematic circuit diagram DI 16x24VDC HA 18 Equipment Manual 10 2020 A5E39265608 AD ...
Страница 36: ...Technical specifications DI 16x24VDC HA 36 Equipment Manual 10 2020 A5E39265608 AD ...