Building Technologies
Electrical features of inputs & outputs
2016-02-22
8
Electrical features of inputs & outputs
8.1 Digital
inputs
Digital inputs are not electrically isolated from the system electronics.
Mechanical contacts must be volt-free.
Electronic switches must comply with SELV or PELV standards.
Technical data
Contact sensing voltage
DC 17...25 V
Contact sensing current
1.0...1.6 mA (initial current 6...10 mA)
Insulation resistance with
contacts closed
Max. 200 Ohm (TX-I/O)
Max. 100 Ohm (DXR2)
Contact resistance with contacts open Min. 50k
8.2 Analog
inputs
8.2.1
Passive resistance sensors and resistance transmitters
The temperature sensors register the temperature by means of a nickel or platinum
wire or a semiconductor which change their resistance in relation to the
temperature.
Key:
R Sensor signal (resistance)
T Actual temperature
The table below shows the resistance of the supported sensor elements as a
function of the temperature.
Temp
AI Ni1000
AI Ni1000 AI Pt1K375 AI Pt1K385
AI T1
AI NTC100K AI NTC10K AI NTC3K
TCR 5000
(
LG-Ni 1000)
DIN
TCR 3750
(USA)
TCR 3850
(Europe)
(PTC)
Beta 3891
Ratio 9.062
Beta 3890
Ratio 9.065
(DXR2 only)
EN60751
°C
°F
Ohm
Ohm
Ohm
Ohm *)
kOhm
kOhm
kOhm
-40
-40
830.8
791.3
846.6
842.7
1'840.4
336.487
101.583
-30
-22
871.7
841.5
885.1
882.2
1'934.6
176.974
53.194
-20
-4
913.5
893.0
923.5
921.6
2'030.3
97.080
29.118
-10
14
956.2
945.8
961.8
960.9
2'127.6
552.830
55.332
16.585
0
32
1'000.0 1'000.0
1'000.0
1'000.0
2'226.4
326.329
32.650
9.795
10
50
1'044.8 1'056.0
1'038.0
1'039.0
2'326.9
198.958
19.904
5.971
20
68
1'090.7 1'112.0
1'076.0
1'077.9
2'429.1
124.920
12.494
3.748
30
86
1'137.6 1'171.0
1'113.8
1'116.7
2'532.9
80.567
8.057
2.417
40
104
1'185.7 1'230.0
1'151.4
1'155.4
2'638.5
53.256
5.326
1.598
50
122
1'235.0 1'291.0
1'189.0
1'194.0
2'745.9
36.010
3.602
1.081
60
140
1'285.4 1353.4
1'226.4
1'232.4
2'855.1
24.864
2.488
0.750
70
158
1'337.2 1417.2
1'263.8
1'270.8
2'966.2
17.505
1.752
0.530
Typical sensing
current
1.1
1.1
1.1
1.1
1.1
0.16
0.7
1.0
*) Not measurable with ohm meter
Supported only with reduced hum injection (details see 7.1.2)
Measured value
acquisition and
measured signal
Resistance table