Bus topologies
Caution: The bus technology is not to be confused with network structure.
It may, however, make sense to establish an analogous tree topology to the
network structure.
In the Konnex world tree, line and star topologies are freely interchangeable.
Ring or circle topologies are not permitted.
Tree
Line
Koppler
Gerät
Star
Ring / circuit (PROHIBITED)
4.5.3
Bus lengths and distances
The indications for distances and line lengths in a network are designed for bus
cables specified by KNX.
Distance of two bus power supplies
min. 200 m.
Distance of a bus device from the next
Bus power supply
max. 350 m.
Distance between two bus devices
max. 700 m.
Total length of all lines on one line
max. 1,000 m.