161/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
Integrate RXB in DESIGO/Synco
28 Feb 2009
15.4 Case 4: Display in DESIGO/Synco,
with shared Synco time scheduler
•
Communication:
– between controllers
LTE mode via zones
– with DESIGO:
Individual addressing or S-Mode
– with ACS:
Individual addressing
•
RXB display:
DESIGO and ACS
•
Synco display:
DESIGO and ACS
•
RXB time scheduler:
from Synco
•
Energy demand:
to Synco
•
The DESIGO time scheduler must be disabled by a specialist.
•
In theory simultaneous display via DESIGO and Synco is possible. However,
problems do arise with the manipulation of values (heartbeat, “last one rules”)
Geographical zone
Geographical zone
Geographical zone
Timeswitch zone
Heating demand zone
Cooling demand zone
10
385D
65
PXC...
PXC...
PX KNX
RXB
RXB
RXB
DESIGO
INSIGHT
ALN
FLN
Konnex
Individual addressing
PXM20
Synco
Synco
Synco
ACS7...
STOP
Important note