106/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Control sequences
28 Feb 2009
8.6.1
Configuration and parameterization
Basic functions: see sections 8.1.1 through 8.1.7.
The outside temperature is transmitted to the room controller via the KNX bus.
See "Outside air temperature via Konnex bus (FNC10, FNC12, FNC18)", page 80 .
Select
Sequences, Other setpoints:
Select
Sequences
,
Other setpoints:
HandyTool
See Parameters in the last column of the table below
Parameter outside air supply
Basic
setting
Range
Resolution
HandyTool
parameter
Outdoor temp. min. damper pos.
16°C
10 °C...40°C *) 0,5°C
*073
Outside air damper runtime
150s
0 ... 360s
1s
*074
Min. damper position
0%
0 ... 100%
1%
*075
*)
By temporarily adjusting the setpoint if necessary, the application ensures that
there is a differential of at least 1K between the
Outside air temp. min. damper
pos.
setpoint and the cooling setpoint of the effective room operating mode.
Outside air temperature
ETS3
Professional
ACS
Service