95/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Master/slave
28 Feb 2009
9.1
S-mode
Master
Slave 1
Slave 2
Slave n
GA1
GA3
GA2
GA4
M/S HVAC controller input
M/S Room unit input
M/S HVAC controller output
M/S Room unit output
10
38
5
Z
18
e
n
M/S HVAC controller input
M/S Room unit input
M/S HVAC controller input
M/S Room unit input
M/S HVAC controller input
M/S Room unit input
M/S HVAC controller output
M/S Room unit output
M/S HVAC controller output
M/S Room unit output
M/S HVAC controller output
M/S Room unit output
The following S-mode input and output communication objects are used for
master/slave connection:
Master/slave HVAC controller output (output comm'object)
(company-specific)
Master/slave room unit output (output comm'object)
(company-specific)
Master/slave HVAC controller input (input comm'object)
(company-specific)
Master/slave room unit input (input comm'object)
(company-specific)
You need 4 group addresses (GA1 … GA4) regardless of the number of slaves.
Select
Master/Slave:
KNX
R
CO
Note
ETS3
Professional