88/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Control sequences
28 Feb 2009
Motorized and electromechanic valves
HandyTool
Parameter Basic
setting
Range
Resolution
HandyTool
Running time cool surf valve
150 s
0 ... 360 s
1 s
*052
Offset cooling surface valve
0 s
0 ... 360 s
1 s
*054
8.2.2
Values representing chilled ceiling valve actuator
positions
The position of the chilled ceiling valve is mapped to the bus.
The
Cooling surface output
communication object must NOT be used for applications
for thermal valve actuators to control KNX/EIB valve actuators. With these applications,
the communications objects have
theoretical
valve positions only.
Valve positions are available in the following S-mode communication objects:
Cooling surface output (output communication object)
Flags
R W C T U
Type Send
heartbeat
Value
1 0 1 1 0 5.001
DPT_Scaling
Yes
0...100%
0 = 0%
255 = 100%
If KNX / EIB bus actuators (S-mode) are integrated in DESIGO, the flags must be
checked: delete read access at actuator!
As there are different manufacturers for EIB/KNX bus actuators, the name of the S-
mode communication object varies.
The valve position in LTE mode is transferred as follows:
Cooling surface output (output)
Possible partner function blocks
Known partner
devices
ActPosSetpCoolStageA
Geographical zone
352 HVA
HVAC Valve Actuator
---
STOP
Important!
KNX
R
CO
Note