RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Temperature measurement
28 Feb 2009
7.1.6
Temperature sensor input from Konnex bus
The signal from the sensor connected to the bus takes priority. The signal is not
averaged and no sensor correction (page 115) is done.
Since KNX temperature sensors are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
RaumTemperatur
EffektiveRaumTemperatur
10384Z16en
Room temperature input
Effective room temperature
KNX Temperature sensor
RXB... Room controller
If the room temperature is available as information on the bus, it can be read with one
of the following S-mode communication objects:
Room temperature input (input communication object)
Flags
R W C T U
Type Receive
timeout
Value
0 1 1 1 1 9.001
DPT_Value_Temp
Yes
Floating point (°C)
Subject to the appropriate configuration and integration, the room temperature is read
by the controller immediately after a reset.
For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled"
Room temperature (input)
Possible partner function blocks)
Known partner devices
TempRoom
Geographical zone
321 RTS
Room Temperature Sensor
Siemens:
Synco RMH760
RMU710 / 20 / 30
QAW740
KNX
R
CO
STOP
Note!