70/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Setpoint calculation
28 Feb 2009
HandyTool
See the parameters in the last column of the following table.
Name
Basic setting
Range 1)
Resolution
Parameter
Protection
cooling setpoint
40 °C
10 ... 40 °C
0.5 K
*030
Economy cooling setpoint
35 °C
10 ... 40 °C
0.5 K
*031
Precomfort cooling setpoint
28 °C
10 ... 40 °C
0.5 K
*032
Comfort cooling setpoint
24 °C
10 ... 40 °C
0.5 K
*033
Comfort heating setpoint
21 °C
10 ... 40 °C
0.5 K
*034
Precomfort heating setpoint
19 °C
10 ... 40 °C
0.5 K
*035
Economy heating setpoint
15 °C
10 ... 40 °C
0.5 K
*036
Protection
heating setpoint
12 °C
10 ... 40 °C
0.5 K
*037
1) ACS checks the values / ranges for intersection.
There is no check in ETS and HandyTool.
HandyTool: If setpoints are irrelevant for the application (e.g. heating setpoints for
chilled ceiling), they are hidden, and they are set equal to the Protection setpoints
internally.
For reasons of symmetry, all communication objects are always available.
6.3
Setpoint setting runtime
The setpoints are stored in the EEPROM so that they are retained upon a reset. If the
communication objects
Setpoints heating
and
Setpoints cooling
receive a value
different from the previous value, this is written to the EEPROM. The service life of the
EEPROM depends on the number of write cycles.
The setpoints for
Comfort
,
Precomfort,
and
Economy
, for heating and cooling each, can
also be defined during runtime
as individual values
or
triplets
via the bus.
Economy cooling setpoint
(input communication object)
Precomfort cooling setpoint (input communication object)
Comfort heating setpoint
(input communication object)
Comfort cooling setpoint
(input communication object)
Precomfort heating setpoint (input communication object)
Economy heating setpoint
(input communication object)
Flags
R W C T U
Type Receive
timeout
States
0 1 1 0 0 9.001
DPT_Value_Temp
No
Floating point (°C)
Setpoints heating (input communication object)
Setpoints cooling (input communication object)
Flags
R W C T U
Type Receive
timeout
States
0 1 1 0 0 222.100
DPT_TempRoomSetp
SetF16[3]
No
3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
Setpoints
STOP
Important!
EEPROM service life
KNX
R
CO