6/8

Siemens Building Technologies

Installation guide

CA2Z3884en

Building Automation

08.2001

5

Cables for AC 24 V triac outputs
and AC 24 V supply

The following applies to the cables of devices such as valves, damper actuators and
contactors connected to the triac outputs of the room controller:
– Use twisted, 2-core or multi-core round cable without a screen (standard installation

cable)

– Single conductors must not be used
– The conductors may be routed together with mains cables (AC 230 V), but they

MUST be insulated from the mains in accordance with regulations and in compliance
with SELV requirements.

– These conductors must

NOT be run in the same cable as mains conductors

– For max. cable lengths, see the table below

Cable type

A

Diameter

R

Cable length Lmax [m]

VDE / DIN

AWG

[mm2]

[mm]

[

/km] 8.5 VA

9.5 VA

13 VA 20 VA

40 VA

60 VA

80 VA

100 VA

120 VA

10

5.26

2.59

3.8

420

-

280

180

90

60

45

36

30

YSLY

4.00

2.26

5.0

320

-

210

138

69

46

34

28

23

12

3.10

2.05

6.3

250

-

165

108

52

36

26

21

18

YSLY

2.50

1.80

8.0

200

167

130

86

43

29

22

17

14

14

1.95

1.62

11

160

130

100

68

34

22

17

13

11

LiYYP

1.50

1.40

14

120

100

80

52

26

17

13

10

8.5

16

1.23

1.30

16

100

82

65

42

21

14

10

8.5

7.0

LiYYP

1.00

1.15

20

80

67

53

34

17

11.5

8.6

6.9

5.5

18

0.96

1.02

21

78

64

51

33

16

11.0

8.3

6.6

5.5

LiYYP

0.75

0.98

26

61

50

40

26

13

8.6

6.5

5.2

4.3

20

0.56

0.81

33

45

37

30

20

10

6.4

4.8

3.8

-

LiYYP

0.50

0.80

39

40

33

26

17

8.5

5.8

4.3

-

-

22

0.34

0.64

56

28

23

18

12

5.8

3.9

-

-

-

LiYYP

(G51/G87)

0.28

0.60

64

22

19

15

9.7

4.8

-

-

-

-

LiYYP

0.25

0.57

77

20

-

13

8.6

-

-

-

-

-

24

0.22

0.51

85

18

-

11.5

7.6

-

-

-

-

-

26

0.15

0.40

130

12

-

8.0

5.2

-

-

-

-

-

LiYYP

0.14

0.39

138

11

-

7.5

-

-

-

-

-

-

Содержание DESIGO RXA20.1

Страница 1: ...YR T B1 YC YH Q1 D1 1 D2 D1 2 DESIGOä ä ä ä RXA Installation guide CA2Z3884en 08 2001 Siemens Building Technologies Building Automation ...

Страница 2: ...2 8 Siemens Building Technologies Installation guide CA2Z3884en Building Automation 08 2001 ...

Страница 3: ...ion 08 2001 Installation guide For controller types RXA20 1 RXA21 1 RXA22 1 and RXA29 1 1 Electromagnetic compatibility EMC 4 2 AC 230 V supply cables 5 3 AC 24 V transformer sizing 5 4 Signal cables 5 5 Cables for AC 24 V triac outputs and AC 24 V supply 6 6 Relay outputs 7 Contents ...

Страница 4: ...r supply cables this minimum spacing is not necessary Where interference emitting cables intersect with cables which are susceptible to interference they should cross at right angles To ensure that the cable screen used works to optimum effect its entire circumference must be firmly connected at both ends to structural earth Structural earth refers to the metal housing mounting plate control panel...

Страница 5: ... sensors room units window switches occupancy sensors dew point sensors and electric switches Use twisted 2 core or multi core round cable without a screen standard installation cable Single conductors and ribbon cable must not be used Signal conductors may be routed together with mains cables AC 230 V but they MUST be insulated from the mains in accordance with regulations and in compliance with ...

Страница 6: ...e the table below Cable type A Diameter R Cable length Lmax m VDE DIN AWG mm2 mm Ω km 8 5 VA 9 5 VA 13 VA 20 VA 40 VA 60 VA 80 VA 100 VA 120 VA 10 5 26 2 59 3 8 420 280 180 90 60 45 36 30 YSLY 4 00 2 26 5 0 320 210 138 69 46 34 28 23 12 3 10 2 05 6 3 250 165 108 52 36 26 21 18 YSLY 2 50 1 80 8 0 200 167 130 86 43 29 22 17 14 14 1 95 1 62 11 160 130 100 68 34 22 17 13 11 LiYYP 1 50 1 40 14 120 100 ...

Страница 7: ...ed load and the local installation regulations Fuse ratings depend on the room controller used Please refer to the relevant controller data sheet The cables must be secured with cable restraints The RXA22 1 controller has an additional relay contact Q44 for switch control of an electric heating coil Note the following for this relay contact The maximum resistive load is 1 8 kW Loads above this val...

Страница 8: ...n guide CA2Z3884en Building Automation 08 2001 Siemens Building Technologies Ltd Building Automation Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 Fax 41 41 724 35 22 www landisstaefa com 2001 Siemens Building Technologies Ltd Subject to change ...

Отзывы: