6/8
Siemens Building Technologies
Installation guide
CA2Z3884en
Building Automation
08.2001
5
Cables for AC 24 V triac outputs
and AC 24 V supply
The following applies to the cables of devices such as valves, damper actuators and
contactors connected to the triac outputs of the room controller:
– Use twisted, 2-core or multi-core round cable without a screen (standard installation
cable)
– Single conductors must not be used
– The conductors may be routed together with mains cables (AC 230 V), but they
MUST be insulated from the mains in accordance with regulations and in compliance
with SELV requirements.
– These conductors must
NOT be run in the same cable as mains conductors
– For max. cable lengths, see the table below
Cable type
A
Diameter
R
Cable length Lmax [m]
VDE / DIN
AWG
[mm2]
[mm]
[
Ω
/km] 8.5 VA
9.5 VA
13 VA 20 VA
40 VA
60 VA
80 VA
100 VA
120 VA
10
5.26
2.59
3.8
420
-
280
180
90
60
45
36
30
YSLY
4.00
2.26
5.0
320
-
210
138
69
46
34
28
23
12
3.10
2.05
6.3
250
-
165
108
52
36
26
21
18
YSLY
2.50
1.80
8.0
200
167
130
86
43
29
22
17
14
14
1.95
1.62
11
160
130
100
68
34
22
17
13
11
LiYYP
1.50
1.40
14
120
100
80
52
26
17
13
10
8.5
16
1.23
1.30
16
100
82
65
42
21
14
10
8.5
7.0
LiYYP
1.00
1.15
20
80
67
53
34
17
11.5
8.6
6.9
5.5
18
0.96
1.02
21
78
64
51
33
16
11.0
8.3
6.6
5.5
LiYYP
0.75
0.98
26
61
50
40
26
13
8.6
6.5
5.2
4.3
20
0.56
0.81
33
45
37
30
20
10
6.4
4.8
3.8
-
LiYYP
0.50
0.80
39
40
33
26
17
8.5
5.8
4.3
-
-
22
0.34
0.64
56
28
23
18
12
5.8
3.9
-
-
-
LiYYP
(G51/G87)
0.28
0.60
64
22
19
15
9.7
4.8
-
-
-
-
LiYYP
0.25
0.57
77
20
-
13
8.6
-
-
-
-
-
24
0.22
0.51
85
18
-
11.5
7.6
-
-
-
-
-
26
0.15
0.40
130
12
-
8.0
5.2
-
-
-
-
-
LiYYP
0.14
0.39
138
11
-
7.5
-
-
-
-
-
-