Siemens CSI Host Driver Скачать руководство пользователя страница 1

Installation Instructions

Document No. 565-718

December 15, 2009

CSI Host Driver for PXC Modular

These installation instructions cover the connection of
the CSI Host Driver to the CSI System. For hardware
installation of the PXC Modular, see document
number 553-638.

Product Description

The CSI Host Driver enables communication
between the APOGEE

®

Automation System and the

CSI system.

Product Numbers

PXC00-PE96.A

PXC Modular RS-485 or Ethernet
ALN, 96 FLN nodes

PXC00-E96.A

PXC Modular with BACnet/IP
ALN and BACnet MS/TP ALN, 96
FLN nodes

PXC100-PE96.A

PXC Modular RS-485 or Ethernet
ALN, TX-I/O Support, 96 FLN
nodes

PXC100-E96.A

PXC Modular BACnet/IP ALN
and BACnet MS/TP ALN, TX-I/O
Support, 96 FLN nodes

PXX-485.3

Expansion Module, three RS-485
FLN connections

LSM-INT-CSIHOST

License for CSI Host PXC
Modular Driver

Accessories

538-670

Trunk Interface II, 115V

538-675

Trunk Interface II, 230V

536-004

Modem Cable, DB-9 Female/DB-25
Male, Serial

Warning/Caution Notations

WARNING:

Personal injury/loss of life may occur if you
do not follow the procedures as specified.

CAUTION:

Equipment damage or loss of data may
occur if you do not follow the procedures
as specified.

Expected Installation Times

The expected installation time is 30 minutes.

Required Tools and Materials

Flat-blade screwdriver (1/8-inch blade width).

Wire strippers.

Cabling and connectors. See the

Connecting

the CSI Host Driver to the CSI System

section.

CAUTION:

Always wear an electro-static discharge
wrist strap and discharge accumulated
static before touching field panel
components.

Prerequisites

Driver hardware is installed according to its
respective installation instructions.

FLN Termination blocks installed, if any.

Depending on the type of installation, other
prerequisites may have to be completed.

Item Number: 565-718, Rev. AA

Page 1 of 4

Содержание CSI Host Driver

Страница 1: ...dular Driver Accessories 538 670 Trunk Interface II 115V 538 675 Trunk Interface II 230V 536 004 Modem Cable DB 9 Female DB 25 Male Serial Warning Caution Notations WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Expected Installation Times The expecte...

Страница 2: ...e II per diagram in Figure 1 or Figure 2 FLN DRIVER S EACH FLN CONNECTOR REQUIRES RS 485 TRUNK CABLE MAX 4000 ft 1200 m STANDARD 24 AWG LOW CAPACITANCE GROUND WIRE TO EARTH P N 538 583 POWER PACK TRUNK INTERFACE II GW1173R3 RS 232 PORT 25 PIN FEMALE RS 232 PORT 9 PIN MALE POWER TAPE BACK SHIELD FLN S IF DRIVER IS LESS THAN 50 CABLE FEET 15 m FROM CSI PANEL PLACE THE TRUNK INTERFACE II IN THE MBC E...

Страница 3: ...3 RS 232 PORT 25 PIN FEMALE PORT A POWER TAPE BACK SHIELD FLN S 1 2 IF DRIVER IS LESS THAN 50 CABLE FEET 15 m FROM CSI PANEL PLACE THE TRUNK INTERFACE II IN THE MBC ENCLOSURE 2 3 7 25 PIN MALE TO 9 PIN FEMALE P N 536 004 TO CSI LAN 78010 HOST TAP 9 PIN RIBBON CABLE CSI PART CBL004 NULL MODEM CONNECTOR PORT B TB2 CABLE 9 PIN MALE TO 9 PIN MALE Figure 2 Connecting the Driver to the CSI System via 78...

Страница 4: ...sign improvements are introduced Product or company names mentioned herein may be the trademarks of their respective owners 2009 Siemens Industry Inc Siemens Industry Inc Your feedback is important to us If you have Document No 565 718 1000 Deerfield Parkway comments about this document send them to Country of Origin US Buffalo Grove IL 60089 4513 SBT_technical editor us sbt siemens com Page 4 of ...

Отзывы: