&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
5-8
A5E00105492-03
([DPSOH
The figure below shows the arrangement of eight signal modules in an S7-300
assembly.
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
CPU
PS
SM1 SM2 SM3 SM4 SM5 SM6 SM7 SM8
Figure 5-4 Rack with eight signal modules
VHHDOVR
Arranging Modules on Multiple Racks
$UUDQJLQJ0RGXOHVRQ0XOWLSOH5DFNV
([FHSWLRQV
With CPU 312 and CPU 312C, only a single-row configuration on a rack is
possible.
8VLQJLQWHUIDFHPRGXOHV
If you are planning a structure distributed between multiple racks then you will
need interface modules (IM). Interface modules route the backplane bus of an
S7-300 to the next rack.
The CPU is always located on rack 0.
Table 5-4
Interface modules - Overview
&KDUDFWHULVWLFV
7ZRRUPRUHURZV
/RZFRVWURZFRQILJXUDWLRQ
Send IM in rack 0
IM 360
Order No.: 6ES7 360-3AA01-0AA0
IM 365
Order No.: 6ES7 365-0AB00-0AA0
Receive IM in rack 1 to 3
IM 361
Order No.: 6ES7 361-3CA01-0AA0
IM 365 (hardwired to send IM 365)
Maximum number of
expansion modules
3
1
Length of the connecting
cables
1 m (6ES7 368-3BB01-0AA0)
2.5 m (6ES7 368-3BC51-0AA0)
5 m (6ES7 368-3BF01-0AA0)
10 m (6ES7 368-3CB01-0AA0)
1 m (hardwired)
Remarks
-
Rack 1 can only receive signal
modules; total current load is limited
to 1.2 A, whereby the maximum for
rack 1 is 0.8 A
These restrictions do not apply to
operation with interface modules
IM 360/IM 361
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...