Engineering via SICAM WEB
398
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
9.1.11.5.5 Command Output
Standard Command Output
For the output of standard commands (
OC
) an appropriate digital output module must be
equipped, and the DO signals to be used must be configured.
Common Settings:
•
Monitor pulse duration
The command output time defines how long the actuator is actuated. The output time can
be set for each data point with the parameter
output_t
.
•
Monitor return information
The return information monitoring is used to limit the command output to the output time
required by the process. The return information monitoring can be activated for each data
point with parameter
RS_Mon_t
.
•
Procedure for the command transmission according to IEC 60870-5-101/104
The procedure for "direct command" is set by means of the parameter
select_execute_t
=
0
.
The procedure for "select and execute command" is set by means of the parameter
select_execute_t
>
0
. The parameterized value specifies, within which time the execute
command must be received following the selection command.
You find the exact information on the command output in the manual
SICAM RTUs Common
Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Pulse Com-
mands", section "Functions Independent on the Hardware of the System Element"
.
Assignment Return Information to Pulse Command
This function coordinates binary information and pulse commands that are acquired or output
on SICAM TM I/O Modules. You find the exact information thereto in the manual
SICAM RTUs
Common Functions Peripheral Elements According to IEC 60870-5-101/104, chapter "Return
Information to Pulse Command Assignment"
.
•
Parameter-settable assignment
The assignment of an information (DI signal) to a pulse command (DO signal) is adjusta-
ble through the 5-digit address of the return information (parameters
RS_Image_CASDU1
,
RS_Image_CASDU2
,
RS_Image_IOA1
,
RS_Image_IOA2
,
RS_Image_IOA3
).
No assignment takes place if the parameters are set to the value
255
(default value) the
target device utilizes the fixed assignment.
•
Predefined assignment
If the equipped sequence of I/O Modules is suitable, an information is assigned automati-
cally to a command. Otherwise no assignment takes place. You find the exact assignment
in the following table.
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......