Installation and Circuitry
186
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
6.4.6
Separating of Master Module and I/O Coupling Module
If you need to separate a CP-8000 from the I/O coupling module (e.g. spare part replace-
ment), proceed as follows:
1.
Separate the external I/O Modules from the Master Module.
2.
Remove the Master Module including the coupling module from the DIN-rail).
3.
Loose at first the 4 clamps of the coupling module which are arrested at the housing.
4.
Loose the 3 clamps which are arrested inside the housing.
Use a proper tool (e.g. a small slotted screwdriver).
5.
Now you can demount the TM I/O coupling module.
6.
Cover the holes of the TM bus with a label.
Note
Above illustrations show the separation of a SICAM TM I/O coupling module from a CP-8000.
The separation of a for SICAM I/O coupling module works the same way.
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......