Compatibility with the previous product
7.3 Compatibility in the user program in DP mode
CP 342-5 / CP 342-5 FO
40
Manual, 10/2011, C79000-G8976-C146-09
Topic / relates to
Response of the device types
CP 342-5 6GK7 342-5DA00-0XE0
CP 342-5 6GK7 342-5DA01-0XE0
New response of the device types
CP 342-5 6GK7 342-5DA02-0XE0
CP 342-5 6GK7 342-5DF00-0XE0
CP 342-5 6GK7 342-5DA03-0XE0
11.
Deterministic sending / receipt
of data - coordination between
CPU and CP/PROFIBUS
In cyclic DP mode, the job
confirmation on the program block
interface includes the confirmation
of the transfer to PROFIBUS.
In cyclic DP mode, the processing cycle on
the CPU is separate from the processing
cycle on the CP.
Send data: The confirmation of the job
includes no confirmation of the successful
transfer to PROFIBUS.
Receive data: It is possible that the same
data was received several times.
12.
Jobs with DP_SEND and
DP_RECV
1)
DP slave mode:
To start job processing, the
program blocks DP_SEND and
DP_RECV must be activated at
least once.
DP master mode:
To start received data processing,
the program block DP_RECV must
be activated at least once.
Depending on the use, it is adequate to
activate program block DP_SEND or
DP_RECV to activate job processing.
In DP master mode, at least of the two
program blocks must be activated at least
once.
13.
Receive buffer length to short
for AG_RECV
If the receive buffer is too small,
data is received until the buffer size
is reached.
The call is acknowledged with error
code 8185
H
.
If the receive buffer is too small, no data is
received.
The call is acknowledged with error code
80B1
H
.
14.
Responder functionality of the
DP master (class 1;
DP master (class 2) passes
jobs to DP master (class 1))
Functions:
"DDLM_GET_Master_Diag
"
"DDLM_Act_Param"
- supported by DP master as
responder -
- DP master without responder functionality -
1)
See also the STEP 7 online help on the SIMATIC NET program blocks for PROFIBUS DP.
Содержание CP 342-5
Страница 6: ...Product overview and notes CP 342 5 CP 342 5 FO 6 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 14: ...Requirements for use 2 3 Programming CP 342 5 CP 342 5 FO 14 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 22: ...Displays and operator controls 4 2 Mode selector CP 342 5 CP 342 5 FO 22 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 50: ...References B 3 On programming CP 342 5 CP 342 5 FO 50 Manual 10 2011 C79000 G8976 C146 09 ...