Further notes on operation
6.3 Interface in the user program
CP 342-5 / CP 342-5 FO
34
Manual, 10/2011, C79000-G8976-C146-09
6.3
Interface in the user program
Status displays with the program block AG_SEND
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR STATUS
Meaning
0
1
8315
H
Possible additional meaning:
This error code can also occur with bus problems (for example physical
disturbances due to bad cable connections or different settings for the transmission
speed on the nodes).
Status displays with the program block DP_DIAG
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR STATUS Possible
with DTYPE
Meaning
1
0
0000
H
0, 1
and 4-9
Job completed without error
Note:
With DTYPE 2, 3 and 10, error-free execution is indicated by a status
code other than "0". Below (see table DP_DIAG codes in /4/ (Page 48)),
you will see the detailed status codes for error-free execution for the
range:
82XX
H
If an error occurs in execution, you receive status codes in the following
ranges:
80XX
H
, 83XX
H
, 8FXX
H
1
0
8248
H
2, 3, 10
Job completed without error
Note: This is the default code for the named diagnostics types if there is
no special situation to signal.
6.4
Other information available about the CP
FAQs on the Internet
You will find detailed information (FAQs) on using the PROFIBUS S7-CPs at the following
Internet address (entry type: FAQ):
10805945 )
Содержание CP 342-5
Страница 6: ...Product overview and notes CP 342 5 CP 342 5 FO 6 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 14: ...Requirements for use 2 3 Programming CP 342 5 CP 342 5 FO 14 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 22: ...Displays and operator controls 4 2 Mode selector CP 342 5 CP 342 5 FO 22 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 50: ...References B 3 On programming CP 342 5 CP 342 5 FO 50 Manual 10 2011 C79000 G8976 C146 09 ...