Properties / services
1.2 Communications services
CP 342-5 / CP 342-5 FO
10
Manual, 10/2011, C79000-G8976-C146-09
●
S7 communication and PG/OP communication
–
PG functions with uploading / downloading of FM modules, configuration / diagnostics
and routing
–
Operator control and monitoring functions (HMI)
Multiplexing TD/OP connections
When multiplexing OP connections, the following acyclic services are supported:
- read once
- write once
- read system status list
–
Client and server for data exchange via communication blocks on S7 connections
configured at both ends
The following blocks / functions are available:
BSEND FB 12, BRCV FB 13,
PUT FB 14, GET FB 15
USEND FB 8, URCV FB 9
C_CNTRL FC 62
You will find a more detailed description in /5/ (Page 49)
Note
The partner station can be an S7-300, S7-400 or PG/PC application with SIMATIC
NET OPC server; raw data tags using BSEND/BRECV to WinCC are not supported.
–
Server for data exchange on connections configured at both ends without
communications blocks on the S7-300 / C7-300 station
●
Open communications services (SEND/RECEIVE interface) over FDL connections of the
following type:
–
Specified FDL connections
–
Free layer 2 connections (SDA, SDN)
–
Broadcast
–
Multicast
The services of the CP 342-5/342-5 FO listed here can be used independently at the
same time.
Содержание CP 342-5
Страница 6: ...Product overview and notes CP 342 5 CP 342 5 FO 6 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 14: ...Requirements for use 2 3 Programming CP 342 5 CP 342 5 FO 14 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 22: ...Displays and operator controls 4 2 Mode selector CP 342 5 CP 342 5 FO 22 Manual 10 2011 C79000 G8976 C146 09 ...
Страница 50: ...References B 3 On programming CP 342 5 CP 342 5 FO 50 Manual 10 2011 C79000 G8976 C146 09 ...