Programming
03/03
CP 243-1 IT
J31069-D0429-U001-A0-7618
100
Call:
ETHx_XFR
START
EN
DONE
Done
Chan_ID
CHANNEL
ERR
Error
Data
DATA
Abort
ABORT
Always_On
START_BIT
Fig. 11
Call of the subprogram ETHx_XFR
Input parameters:
Name
Type
Meaning
START
BOOL
Input condition for triggering a read/write job
0:
Don't trigger read/write job
1:
Trigger read/write job
Chan_ID
BYTE
Number of the channel via which the data is to
be accessed. This channel must be configured
as client.
Value range: 0 to 7
Data
BYTE
Number of the channel-specific data block from
the configuration which describes the read/write
job to be executed.
Value range: 0 to 31
Abort
BOOL
Input condition for canceling a data access
0:
Don't cancel data access
1:
Cancel data access
Table 21
Input parameters (ETHx_XFR)