28/30
Siemens
Climatix touch
panel
A6V10445442
_en--_a
Building Technologies
Technical specifications
2015-06-30
The RS485 connection is shown as an example.
Note:
Accessory POL0C1.45/STD (touch panel-controller communication cable)
has an RJ45 connector. To connect touch panel to Climatix controller
RS485/RS232 port, cut-off plug and connect 3 wires. If a customized cable is used,
ensure that the cable length is less than 3 m.
8.3
LED indicators
The three LED indicators are located on the front of the Climatix touch panel.
Marking Indicator name
Color
Mode
Description
Power supply
Green
On
Powered on
Off
No power
Operation
Yellow
On
No detected fault
Off
CPU fault detected in the device
Communication
Yellow
Flashing
Communication in progress
Off
No communication
8.4
DIP switches
The DIP switches are located on the back of the Climatix touch panel.
DIP switches
1)
(1 – 5)
Function
00000
Normal operation mode
01000
Setting mode
10000
Calibrate the touch screen
10100
Enter Android system
00100
Firmware upgrade mode
1)
DIP switch status: ON=1, OFF=0
Communication cable
(POL0C1.45/STD)