35 / 38
Siemens
Climatix HMI-TM
CB1P3917en02
Building technologies
3BFunctions and operations
2015-07-02
7. Select the newly created icon. And click
Select
and
Copy
. Then click
button
to return to
Language
tab as follows.
Enumeration icons:
8. Double-click the English column of
iHeat*iCool
. Right click the mouse and
select
Paste
to fill in the newly created icon.
9. Save the page and generate HMI file.
Refer to Help of SCOPE tool for further information about Iconic mode engineering.
4.12 Firmware update
The procedure of upgrading firmware is as follows:
1. Store the
POL12291.bin
file in the root directory of the SD card and insert
the SD card to the controller.
2. Connect the HMI-TM to the controller.
3. Press and hold key
ESC
to enter the following page.
4. Select
HMI settings
and press key
ENTER
. Then the following page will
be displayed: