PXL Conventional Fire Alarm Control Panel
Operation
38
Responding to a Supervisory Condition
HOW THE SYSTEM ANNUNCIATES SUPERVISORIES
When a supervisory alarm is detected, the system causes the
SUPERVISORY
LED and one of the zone
LEDs to flash and the
systems internal audible to sound.
TO ACKNOWLEDGE SUPERVISORIES
1. Unlock and open the door.
2. Press the ACKNOWLEDGE button to acknowledge the
supervisory condition. The system
SUPERVISORY
LED and the
zone
LEDs on the front panel stop flashing and remain on and
the systems internal audible silences.
TO RESET
The system operator should RESET the system by pressing the
RESET button. (The system will not reset until all alarms,
supervisories, and troubles are acknowledged and all conditions are
returned to normal.)
Responding to a Trouble Condition
HOW THE SYSTEM ANNUNCIATES TROUBLES
When a trouble is detected, the system causes the
TROUBLE
LED
and the appropriate
Zone TROUBLE
LEDs on the front panel to
flash and the systems internal audible to sound.
TO ACKNOWLEDGE TROUBLES
1. Unlock and open the door.
2. Press the ACKNOWLEDGE button to acknowledge the troubles.
The system
TROUBLE
and the individual zone
TROUBLE
LEDs
on the front panel stop flashing and remain on. The systems
internal audible silences.
NOTE:
Acknowledged troubles will be reported again in 24
hours if they are not cleared.
TO RESET
The system operator should RESET the system by pressing the
RESET button. (The system will not reset until all alarms,
supervisories, and troubles are acknowledged and all conditions are
returned to normal.)