E3X100 Master module (superseded by E3X101)
33
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
17 Programming switch ”S3”: Choose "I-Bus address battery charger"
To set I-Bus address for the
Function unit ”Charge /monitor battery”
. This unit is
an I–Bus user (as e.g. line module) and must have an individual address (number).
This is set on programming switch ”S3”.
Maximum 16 I-Bus devices
Function / I-Bus address
Programming switch S3
No.
S3-1 S3-2 S3-3 S3-4 S3-5
S3-6
0
Module out of commission (unused)
off
off
off
off
off
off
1
I-Bus user number
1
on
off off off off
off
2
2 off
on
off off off
off
3
3
on
on
off off off
off
4
4 off
off
on
off off
off
5
5
on
off
on
off off
off
6
6 off
on
on
off off
off
7
7
on
on
on
off off
off
8
8 off
off
off
on
off off
9
9
on
off off
on
off off
10
10 off
on
off
on
off off
11
11
on
on
off
on
off off
12
12 off
off
on
on
off off
13
13
on
off
on
on
off off
14
14 off
on
on
on
off off
15
15
on
on
on
on
off off
16
16
off off off off
on
off
”S3–1...6” are set to ”off” at the factory
18 Programming switch "S2": Choose "Battery type"
To set temperature compensation according to information from the various battery
manufacturers
Possible battery variants
Programming switch S2
Var.
Battery manufacturer
Battery model
S2-1
S2-2
S2-3
S2-4
0
off off off off
1
on
off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage
Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on
off off
3 Genesis
G12V120W15
on
on
off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off
on
off
5
Phoenix (Korea)
FNC 12..0
on
off
on
off
6 Yuasa
NP..–12B
off
on
on
off
7 Sonnenschein
Dryfit
A212/..G5
on
on
on
off
8 Power–Sonic
PS12..0
off off off
on
9 Hagen
Drysafe
HDS–12..0NB
on
off off
on
10 Sonnenschein
Dryfit
A512/..G5
off
on
off
on
11
ALARMCOM (FIAMM) 1)
FG...
on
on
off
on
12
off off
on
on
13
on
off
on
on
14
off
on
on
on
15
on
on
on
on
”S2” is set to variant 11 (ALARMCOM) at the factory
1) available from index ’CD' onwards
7.5.1
Floating charging voltage as a function of temperature
Î
see E3X101 page 43
19 Battery charging section