E3X100 Master module (superseded by E3X101)
27
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
7
E3X100 Master module
(superseded by E3X101)
7.1 Overview
z
Main evaluating unit for the
CS1140
series of fire detection control units with the
function of ”Main CPU”
Î
With small systems, the B3Q... control console can also take over the ”Main
CPU” function.
z
Processes up to 16 I–Bus modules
z
Various interfaces, control inputs, control outputs and supply outputs
z
EPROM as program memory
z
RAM depending on application
z
Lithium battery for RAM buffering
z
Integrated battery–charger and monitoring function unit as I–Bus module
z
Integrated emergency operation electronics
z
Card format 366.8 mm x 200 mm
7.2 Application
Processing capacity see –> document ’Planning’ (1076 EP5, 008725 EP7F-Z1)
For larger systems with stations
CC1142
or
CC1143
.
.
According to system size (table of quantities) choose the corresponding
EPROM+RAM set:
–
for
CC1142
–>
CCQ00xxx
(EPROM set 2x 512Kx8Bit)
Z3S070
(RAM set 2x 512Kx8Bit)
–
for
CC1143
–>
CCW00xxx
(EPROM set 2x 512Kx8Bit)
Z3S070
(RAM set 2x 512Kx8Bit)
K3N010
(RAM board 1x 1MB)
Recommended EPROMs: 27C040, 27C4001 (512Kx8Bit, 100 ns, DIP32)
Terminal blocks X15 and X16 (20 terminals each).
With EMI protect.
.
–
mounted on module chassis
–
for the connection of the prefabricated cable to connection level, or
–
for direct connection of the periphery
Terminal block X17 (20 terminals)
Only for internal connections
.
–
mounted on module chassis
–
for the connection of the prefabricated cable for battery, temperature sensor and
power unit
Battery terminals (+, –, Centre tap)
Temperature sensor
Card chassis
X15
X16
X17