K3R070 Mimic Display board (superseded by K3R071)
203
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
48.3 Wiring
principle
Control console and Mimic Display board in the immediate vicinity
4 cable set Z3I520 (12 cables each) per K3R070
Equipment 1
Equipment 2
1
48
1
48
Data bus
Data bus
AlgoPilot B3Q...
K1
ST4
K1
ST1
K3R070
ST2
K3R070
K1
ST2
ST1
F12A100: 0.4 m / F12A470: 1.5 m
24 V supply
Mimic Display board separate from the control console
Parallel derivation
4 cable set Z3I520 (12 cables each) per K3R070
permissible
Equipment 1
Equipment 2
1
48
1
48
Data bus
Data bus
K7
ST4
K3R070
K1
K2
ST2
K3R070
K1
ST1
ST2
AlgoPilot B3Q...
Adapter Z3I350
max. 1000 m
24 V supply
Note:
–
Max. 24 units B3R051 or K3R070 (also mixed) possible with max. 8 different addresses
–
Remove resistor array except on
one
unit (–> see page 205)