B3Q6.. / 565 Control terminal AlgoPilot
179
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
43
B3Q6.. / 565 Control terminal AlgoPilot
43.1 Overview
240 x 128 dots illumination yellow
240 x 128 dots illumination yellow
240 x 128 dots illumination yellow
B3Q660 (Standard)
B3Q670 (Australian)
B3Q680 (Nordic)
240 x 128 dots illumination yellow
240 x 128 dots illumination yellow
–
operation and designation of indicators,
see document 004598
–
principle of the insertable inscription strips
see page 181
–
Templates for inscription strips see docu-
ment 006516 (only if no inscription strips
are available)
–
details for ordering see document 'Plan-
ning' (008725 EP7F-Z1)
B3Q685 (CH)
(as B3Q680 but with KABA lock)
B3Q565 (China)
z
Control terminal for the fire detection series
CS1140
z
Can simultaneously also be used as ’main-CPU’
z
For full system operating
z
Can be used for
single
or
multi
AREA operating
z
Emergency operating facility integrated
z
Flash–ROM 2MBx8Bit as program memory, programming via Flash-Tool (PC)
z
SRAM for user data and standard text
z
Selectable ground fault monitoring, detected via master module E3X10. or via
control module E3G070 (for application details see chapter 6)
z
Operating access via password and/or key switch
z
Insertable inscription strips in different languages
z
to be built into the housing of the control unit or remote located in separate hous-
ing
43.2 Key
data
Operating voltage
18...45 VDC
Quiescent current (illumination of the LCD inactive)
100 mA (24 V)
Alarm current
330 mA (24 V)
Maximum current (LCD backlight lamp test)
420 mA (24 V)