Multi-Pump Wizard (P1.18)
The Multi-Pump Wizard is activated in the Quick Setup (M1) menu. This wizard assists with configuring the drive for
use with PID Controller 1, and then asks the most important questions for setting up a multi-pump system.
The following steps are required to successfully complete the Multi-Pump Wizard:
Step
Parameter/Question
Settings
1 – 14
Same as PID Mini-Wizard
15
Number of Motors (P3.14.1)
1 to 4
16
Interlock Function (P3.14.2)
Not Used
Enabled
17
Auto-change (P3.14.4)
Disabled
Enabled
If the Auto-change function is enabled, the following will display. Otherwise, the wizard jumps directly to Step 21:
Step
Parameter/Question
Settings
18
Include FC (P3.14.3)
Disabled
Enabled
19
Auto-change Interval (P3.14.5)
0.0 to 3000.0 h
20
Auto-change Frequency Limit (P3.14.6)
0.0 to 60.0 Hz
21
Bandwidth (P3.14.8)
0 to 100%
22
Bandwidth Delay (P3.14.9)
0 to 3600 s
After this, the keypad displays the digital input and relay output configuration done by the application. It is
recommended that these values are written down for future reference.
The Multi-Pump Wizard is now complete.
Fire Mode Wizard (P1.20)
The Fire Mode feature of the drive is designed to place the drive in a mode that ignores all commands from the
keypad, fieldbuses, and the personal computer tool. In addition, the drive will ignore all alarms and faults of the
drive and continue providing frequency to the attached motor. This is designed for instances when the destruction of
equipment is better than loss of life. The Fire Mode feature can be operated so that the PID loop is still in control of
the attached motor. The Fire Mode Wizard allows for easy commissioning of the Fire Mode function.
The Fire Mode Wizard is activated in the Quick Setup (M1) menu. The wizard assists with configuring the drive for
use with the Fire Mode feature.
NOTE:
The warranty is void if the Fire Mode function is activated. Test Mode can be used to
test the Fire Mode function without voiding the warranty. Read important information
about the password and warranty issues in Chapter 4 before you proceed.
Test Mode can be used to test the Fire Mode function without voiding the warranty.
The Fire Mode Wizard can be initiated by choosing Activate for Fire Mode Wizard (P1.20) in the Quick Setup (M1)
Menu.
The following steps are required to successfully complete the Fire-Mode Wizard: