Chapter 4 - Parameters and Menu Structure
Parameters (M3)
108 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Application Settings (M3.17)
The Applications Settings contain specific application information and are presented in the following table:
Table 72: Application Settings.Information.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.17.1
Password
0
65000
0
Location for entering a password to
the unit that will grant access to
development parameters.
P3.17.2
kW/HP Selection
kW
HP
HP
1198
Defines the selection of the unit’s
power type parameters. Selectable
for kilowatt or horse power.
P3.17.3
°C/°F Selection
ºC
ºF
ºF
1197
Defines the selection of the unit’s
temperature type parameters.
Selectable for Celsius or
Fahrenheit.
P3.17.4
ByPass
Disabled
Electronic
Disabled
1809
Defines the bypass option
connected to the drive.
NOTE: To set the proper value for
this parameter, it is not
recommended to change this
parameter. This parameter is set
during the run of the Bypass Wizard
(P1.21)
Possible settings are as follows:
0 = Disabled
1 = Conventional
2 = Electronic
NOTE: The setting of Disabled
should also be used with all SED2
Migration Bypass Kits.
Bypass (M3.18)
The Bypass settings can only be accessed if Bypass (P3.17.4) is set to Electronic. The best way to set this is by
executing the Bypass Wizard (P1.21). The Bypass settings contain specific information about the Electronic
Bypass configuration.
The bypass settings are presented in the following table: