Technical Description (TED:BSS)
BS-240/241
Information
Base Station System
In order to keep both the acoustic noise and the power consumption of all fans at the
lowest level possible, the fan speeds are (independently of each other) temperature
controlled via integrated sensors (NTC) that monitor the critical hotspots in order to keep
them in an acceptable range.
Furthermore, each fan delivers a fan good/fan bad signal that is processed by the COBA
board (routed via ACTC board in case of a Base Rack/Shelter or the ACTC board and
CAN Bus in case of an Extension-/Service Rack/Shelter).
3.19Heat Exchanger (HEX)
The BS-241 shelters can be equipped either with HEX.
The heat exchangers can only be equipped on the internal side of the door of the BS-241
shelter. The task of a heat exchanger is to transport the heat from inside the shelter to
the outside.
For every Frame in a base or extension shelter one heat exchanger is needed, there-
fore, 3 heatexchangers are always installed in a base or extension shelter for:
–
ACOM Frame
–
Carrier Frame
–
Core Frame
In the service shelter we have three sections, which can be differently equipped with
AC/DC modules, link equipment or backup batteries and then 1 to 3 heat exchangers
are needed, according to the installation of equipment.