Diagnostics
6.2 Parameterization of the diagnostics
ASM 456 interface module
Operating Instructions, 07/2015, J31069-D0162-U001-A6-7618
45
Other ASM operating modes are indicated by the PRE, ERR, ACT, SF and ON LEDs:
ON
SF
PRE_1 ERR_1
ACT_1 PRE_2 ERR_2
ACT_2
Description
On
Off
Off
Off
On
Off
Off
Off
Ramp-up active
Off
On
Off
On
Off
Off
Off
Off
Checksum error at ramp-up
Off
On
Off
Off
Off
Off
On
Off
Firmware invalid
On
On
On
On
On
On
On
On
LED test for approximately 4 seconds;
otherwise firmware fault
Off
On
Off
On
On
Off
On
On
Checksum error at ramp-up
Off
On
On
On
On
Off
On
On
Checksum error of the firmware
Off
On
On
On
On
On
On
On
External RAM defective
Off
On
On
Off
On
On
On
On
DPC-RAM defective
Off
On
Off
On
On
On
On
On
ID error firmware
On
–
Off
1 x flash
every 3 s
Off
Off
1 x flash
every 3 s
Off
ASM successfully ramped up, waiting
for reset command
–
–
–
n x flash-
es
–
–
m x
flashes
–
The last reported fault in the channel
can be seen from the number of flash-
es (n, m).
On
–
–
Flashing
Rapid
flashing
–
Flashing
Rapid
flashing
Firmware update; alternate flashing of
the error LEDs at approximately 1 Hz
– = not relevant
6.2
Parameterization of the diagnostics
In addition to the PROFIBUS standard diagnostics, the ASM 456 offers user-specific
diagnostics data structured in the form of device-related diagnostics.
Along with error messages that are also communicated with command processing,
diagnostics data contain cross-application information such as the start of a firmware update.
The diagnostics data can be read out as follows:
●
As a plaintext display on S7 interfaces.
●
Storage of the diagnostics data with the help of SFC 13 in the data area of an application.
●
Evaluation with FB 125 or FC 125.