Connection
4.5 Connecting an ASM 456 up to functional earth
ASM 456 interface module
32
Operating Instructions, 07/2015, J31069-D0162-U001-A6-7618
Required accessories (optional)
●
M5 x 10 retaining bolt and washers
●
Grounding cable (copper braided cable) with minimum cross-section of 4 mm
2
.
●
Cable lug
Connecting the ASM 456 to functional earth
Standard grounding via the securing screw
Optional grounding via a grounding cable
1.
Mount the module on the grounded, metallic base.
①
Grounded, metallic base
②
Unpainted thread or surface of the nut
1.
Isolate the grounding cable and secure the cable lug.
2.
Screw the cable lug on to the communication module
(M5 grounding screw). The tightening torque is 3 Nm.