7SR210 & 7SR220 Description of Operation
Unrestricted ©2018 Siemens Protection Devices Limited
Page 59 of 94
1
st
Trip (Inst)
2
nd
Trip (Inst)
3
rd
Trip (Inst)
4
th
Trip (Delayed)
4
th
Dead Time
3
rd
Dead Time
2
nd
Dead Time
1
st
Dead Time
4.1.2
Auto Reclose sequences
The CONTROL & LOGIC>AUTO RECLOSE PROT’N and CONTROL & LOGIC>AUTORECLOSE CONFIG’
menus, allow the user to set independent Protection and Auto Reclose sequences for each type of fault i.e. Phase
Fault (P/F), Derived/Measured Earth Fault (E/F), Sensitive Earth Fault (SEF) or External Protections (EXTERN).
Each Auto Reclose sequence can be user set to up to four-shots i.e. five trips + four reclose sequence, with
independently configurable type of Protection Trip. Overcurrent and earth fault elements can be assigned to any
combination of Fast (
Inst
),
Delayed
or highset
(HS)
trips
.
Deadtime
Delay time settings are independent for each
AR shot. The user has programming options for Auto Reclose Sequences up to the maximum shot count i.e.:-
Inst
or
Delayed
Trip 1 + (
DeadTime 1
: 0.1s-14400s
)
+
Inst
or
Delayed
Trip 2 + (
DeadTime 2:
0.1s-14400s
)
+
Inst
or
Delayed
Trip 3 + (
DeadTime 3
: 0.1s-14400s
)
+
Inst
or
Delayed
Trip 4 + (
DeadTime 4
: 0.1s-14400s
)
+
Inst
or
Delayed
Trip 5 – Lockout.
The AR function recognizes developing faults and, as the shot count advances, automatically applies the correct
type of Protection and associated Dead time for that fault-type at that point in the sequence.
A typical sequence would consist of two
Inst
trips followed by at least one
Delayed
trip. This sequence enables
transient faults to be cleared quickly by the
Inst
trip(s) and permanent fault to be cleared by the combined
Delayed trip. The delayed trip must be ‘graded’ with other Recloser/CB’s to ensure system discrimination is
maintained, ie. that as much of the system as possible is live after the fault is cleared.
A
HS trips to lockout
setting is provided such that when the number of operations of elements assigned as HS
trips reach the setting the relay will go to lockout.
The number of Shots (Closes) is user programmable, note: - only one Shot Counter is used to advance the
sequence, the Controller selects the next Protection characteristic/Dead time according to the type of the last Trip
in the sequence e.g. PF, EF, SEF or EXTERNAL.
Reclose Dead Time
User programmable dead times are available for each protection trip operation.
The dead time is initiated when the trip output contact reset, the pickup is reset and the CB is open.
The CB close output relay is energised after the dead time has elapsed.
Figure 4.1.2-1
Typical Sequence with 3 Instantaneous and 1 Delayed trip
Содержание Argus 7SR21
Страница 1: ...Energy Management 7SR21 7SR22 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...Contents 7SR11 and 7SR12 Page 2 of 2 2018 Siemens Protection Devices Limited ...
Страница 116: ...7SR210 Instrumentation Guide Unrestricted Page 4 of 12 2018 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 117: ...7SR210 Instrumentation Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 12 2 Menu Structure ...
Страница 129: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 5 of 61 1 Function Diagram ...
Страница 130: ...7SR210 Settings Guide Unrestricted Page 6 of 61 2018 Siemens Protection Devices Limited 2 Menu Structure ...
Страница 185: ...7SR210 Settings Guide Unrestricted 2018 Siemens Protection Devices Limited Page 61 of 61 ...
Страница 189: ...7SR220 Instrumentation Guide Page 4 of 20 2017 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 190: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 5 of 20 2 Menu Structure ...
Страница 194: ...7SR220 Instrumentation Guide 2017 Siemens Protection Devices Limited Page 9 of 20 Frequency 0 000Hz ...
Страница 211: ...7SR220 Settings Guide Unrestricted Page 6 of 107 2013 Siemens Protection Devices Limited 1 Function Diagram ...
Страница 277: ...7SR220 Settings Guide Unrestricted Page 72 of 107 2013 Siemens Protection Devices Limited ...
Страница 382: ...7SR220 Technical Manual Chapter 4 Page 2 of 96 2017 Siemens Protection Devices Limited ...
Страница 386: ...7SR220 Technical Manual Chapter 4 Page 6 of 96 2017 Siemens Protection Devices Limited ...
Страница 398: ...7SR220 Technical Manual Chapter 4 Page 18 of 96 2017 Siemens Protection Devices Limited ...
Страница 414: ...7SR220 Technical Manual Chapter 4 Page 34 of 96 2017 Siemens Protection Devices Limited ...
Страница 466: ...7SR220 Technical Manual Chapter 4 Page 86 of 96 2017 Siemens Protection Devices Limited ...
Страница 468: ...7SR220 Technical Manual Chapter 4 Page 88 of 96 2017 Siemens Protection Devices Limited ...
Страница 470: ...7SR220 Technical Manual Chapter 4 Page 90 of 96 2017 Siemens Protection Devices Limited ...
Страница 472: ...7SR220 Technical Manual Chapter 4 Page 92 of 96 2017 Siemens Protection Devices Limited ...
Страница 643: ...Unrestricted ...