Instruction manual AQ101, AQ101D, AQ110P, AQ01
35 (48
)
7.1.6
H
IGH
S
PEED
O
UTPUTS
HSO1,
HSO2
(AQ110P
ONLY
)
Number
2
Rated voltage
250 V DC
Continuous carry
0.5 A
Make and carry for 0.5s
15 A DC
Make and carry for 3s
6 A DC
Make and carry for 20s
2 A DC
Breaking capacity DC, when time constant
L/R=40ms
110W (1A at 110V DC)
Contact material
Semiconductor
7.1.7
B
INARY
O
UTPUT
BO1
Number of outputs
1
Rated voltage
24 V DC (internally supplied)
Maximum burden
20mA / 480 mW
7.1.8
B
INARY
I
NPUTS
BI1,
BI2
Number of inputs
2
Rated voltage
24 or 110 or 220Vdc *
Rated burden
3 mA
*) Refer to the ordering codes.
Binary inputs are galvanically isolated from the device grounding.
Attention shall be paid for avoiding galvanic loops via binary input
ground.