Instruction manual AQ101, AQ101D, AQ110P, AQ01
23 (48
)
3.1.3
S
ET BUTTON
All devices contain a set button in the front panel, which is used for installing the
system, checking the number of connected sensors and units, resetting the device
after trip event and clear the alarm signals.
Figure 3-2: Set button.
Function
Instruction
Indications
Install (add binary input or
sensor amount) the system
configuration
Press the button for 3 seconds
All connected inputs LED’s lit
steadily during installation.
Install (reduce binary input or
sensor amount) the system
configuration
Switch any DIP switch back and
forth one time, press the button
for 3 seconds
All connected inputs LED’s lit
steadily during installation.
Clear the alarm signals
Press the button once
Respective blinking led indicators
turns off
Check the number of installed
sensors and unit connections
(Binary inputs) *
Press the button 3 times within 2
seconds.
Corresponding connected input
LED blinks showing amount of
connected units and sensors.
Reset after trip or sensor or
binary input activation
Press the button once
Corresponding activated signals
and LED’s turns off. Also latched
outputs resets.
Table 3-3: Set button function vs. indication behaviors.
*) Only available at AQ101, AQ101D and AQ110P.
Содержание Arcteq AQ01
Страница 1: ...INSTRUCTION MANUAL AQ101 AQ101D AQ110P AQ01 ...
Страница 44: ...Instruction manual AQ101 AQ101D AQ110P AQ01 44 48 ...
Страница 45: ...Instruction manual AQ101 AQ101D AQ110P AQ01 45 48 ...
Страница 46: ...Instruction manual AQ101 AQ101D AQ110P AQ01 46 48 9 2 AX001 CONNECTION FIBER ...
Страница 47: ...Instruction manual AQ101 AQ101D AQ110P AQ01 47 48 9 3 AQ01 ARC FLASH SENSOR ...